Plan Review Notes For Permit 18050905 |
Permit Number |
18050905 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-05-30 14:49:58 | 1) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE | | MAXIMUM SYSTEM FLOW. THE MAXIMUM FLOW OF THE PUMP FROM | | ITS PUMP CURVE IS NO LONGER ALLOWED TO BE USED IN | | DETERMINING MAXIMUM SYSTEM FLOW RATE PER ANSI/APSP/ICC | | 7 ? 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 EDITION | | ADDRESSES FLOW RATE IN GALLONS PER MINUTE (GPM). IT | | REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES NOT EXCEED | | THE LISTED MAXIMUM FLOW RATE OF THE SUCTION OUTLET | | FITTING ASSEMBLY (DRAIN COVER). | | 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS FOR THE UNBLOCKABLE CHANNEL DRAIN. WPB | | AMEND. TO FBC SEC. 107.2.1. | | 3) SUBMIT TWO COPIES OF THE MANUF. SPECIFICATIONS FOR | | THE POOL PUMP. WPB AMEND. TO FBC SEC. 107.2.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | | | |
|