2018-06-01 15:46:31 | 06/01/2018 PLUMBING 2ND REVIEW**DENIED** |
| |
| *** NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT |
| THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED |
| CORRECTIONS*** |
| |
| YOU HAVE FAILED TO EITHER NOT ADDRESS AT ALL OR NOT IN |
| FULL ANY OF THE COMMENTS FROM THE LAST REVIEW. UNDER FL |
| ST. STAUTE 553.80 (B) ANY PLAN REVIEW THAT IS DENIED |
| FOR THE SAME COMMENTS 3X IS SUBJECT TO A 4X PLAN REVIEW |
| FEE. I WOULD ADVISED YOU TO COME IN FOR A MEETING |
| BEFORE RESUBMITTING AGAIN. |
| |
| |
| |
| A SEPARATE PERMIT APPLICATION IS REQUIRED FOR |
| ELECTRICAL, MECHANICAL, AND FIRE PER FBC 105.1 |
| |
| 1) PROVIDE A FULL PLAN SHOW ALL DIMENSIONS REQUIRED |
| UNDER THE SCOPE OF WORK. PLAN SHALL BE PREPARED SHOWING |
| HOW YOU INTENT TO KEEP THE MASTER BATHROOM IN |
| COMPLIANCE WITH FAIR HOUSING ACT SHOWING ALL THE |
| REQUIRED CLEAR FLOOR SPACES AND NOW EXPANDING THE |
| ACCESSIBLE ROUTE INTO BATHROOM #2 FOR ACCESS TO THE |
| WASHER AND DRYER AS THIS DWELLING WAS DESIGNED UNDER |
| SPECIFICATION B OF THE FHA. 24 CFR 100.205 |
| |
| 2) CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND |
| DRAWN UPON SUITABLE MATERIAL. ELECTRONIC MEDIA |
| DOCUMENTS ARE PERMITTED TO BE SUBMITTED WHERE APPROVED |
| BY THE BUILDING OFFICIAL. CONSTRUCTION DOCUMENTS SHALL |
| BE OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, |
| NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN |
| DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS |
| CODE AND RELEVANT LAWS, ORDINANCES, RULES AND |
| REGULATIONS. FBC 107.2.1 |
| |
| 3) PROVIDE A PLUMBING SANITARY RISER DRAWING AND SHOW |
| HOW YOU INTENT TO CONNECT THE WASHING MACHINE STAND |
| PIPE INTO THE EXISTING DRAINAGE SYSTEM. PLEASE BE |
| ADVISE CONNECTING INTO THE BATHROOM HORIZONTAL WET VENT |
| IS NOT ALLOWED UNDER FBC P 912.1 |
| |
| 4) YOU HAVE NOT PUT A VALUE ON THIS REVISION AND HAVE |
| SIGNIFICANT CHANGES. PROVIDE A SIGNED BONA FIDE |
| CONTRACT SHOW FULL VALUE OF ENTIRE JOB. WPB AMEND TO |
| THE FBC 109.3 |
| |
| 5) PROVIDE WASHER AND DRYER INSTALLATION MANUALS/ |
| SPECIFICATION SHEETS. FBC 107.2.1 |
| |
| 6) SHOW DISTANCE THAT DRAIN IS TO BE MOVE (OFFSET) FROM |
| EXISTING P-TRAP TO STAY IN COMPLIANCE WITH FBC P 1002.1 |
| |
| 7) PROVIDE A DETAIL CABINET DRAWING SHOW FINISHED |
| ELEVATION AT MAX 34" FBC 107.2.1 |
| |
| TIM HUNT |
| PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER |
| CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT |