2018-06-18 17:17:40 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18050851 |
| 6/18/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX= FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVBIDE MECHANICAL PLANS SHOWING ALL |
| REQUIRED ALTERATIONS TO THE EXISTING SYSTEMS TO |
| ACCOMODATE THE NEW FLOOR PLAN LAYOUT AND THE CHANGE OF |
| OCCUPANCY. PLEASE INCLUDE VENTILATUION CALCULATIONS FOR |
| ALL ROOMS AND SPACES IN COMPLIANCE WITH TABLE 403.3.1 |
| FBC M. |
| |
| 2) AS STATED IN COMMENT #1 ABOVE, THE PROPOSED PROJECT |
| APPEARS TO BE A CHANGE OF OCCUPANCY AS DEFINED IN |
| SECTION 202 FBC EX. PLEASE SEE CHAPTER 10 FOR ALL |
| REQUIRED COMPLIANCES, AND INDICATE THE CLASSIFICATION |
| OF WORK ON COVER SHEET T-1 PER SECTION 506 FBC EX. |
| |
| 3) REFER TO SECTION C505.1 FBC EC SND SUBMIT AN ENERGY |
| COMPLIANCE REPORT FOR THWE PROPOSED CHANGE OF |
| OCCUPANCY. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |