Plan Review Notes
Plan Review Notes For Permit 18050851
Permit Number 18050851
Review Stop M
Sequence Number 1
Notes
Date Text
2018-06-18 17:17:401ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18050851
 6/18/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX= FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVBIDE MECHANICAL PLANS SHOWING ALL
 REQUIRED ALTERATIONS TO THE EXISTING SYSTEMS TO
 ACCOMODATE THE NEW FLOOR PLAN LAYOUT AND THE CHANGE OF
 OCCUPANCY. PLEASE INCLUDE VENTILATUION CALCULATIONS FOR
 ALL ROOMS AND SPACES IN COMPLIANCE WITH TABLE 403.3.1
 FBC M.
  
 2) AS STATED IN COMMENT #1 ABOVE, THE PROPOSED PROJECT
 APPEARS TO BE A CHANGE OF OCCUPANCY AS DEFINED IN
 SECTION 202 FBC EX. PLEASE SEE CHAPTER 10 FOR ALL
 REQUIRED COMPLIANCES, AND INDICATE THE CLASSIFICATION
 OF WORK ON COVER SHEET T-1 PER SECTION 506 FBC EX.
  
 3) REFER TO SECTION C505.1 FBC EC SND SUBMIT AN ENERGY
 COMPLIANCE REPORT FOR THWE PROPOSED CHANGE OF
 OCCUPANCY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  