2018-05-25 14:25:23 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) THE OCCUPANCY IS INDICATED AS WAREHOUSE; HOWEVER, |
| MINI SHOWROOMS ARE INDICATED WITH AN OPEN FLOOR SPACE |
| INDICATED AS SHOWROOM. THIS CHANGE OF OCCUPANCY APPEARS |
| TO BE MERCANTILE IN THE LIFE SAFETY CODE. |
| |
| PER NFPA 101, CHAPTER 6, CLASSIFICATION OF OCCUPANCY. |
| |
| 6.1.10.1* DEFINITION ? MERCANTILE OCCUPANCY. AN |
| OCCUPANCY USED |
| FOR THE DISPLAY AND SALE OF MERCHANDISE. |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC FIRE |
| CODE REFERENCES. |
| |
| |
| |
| 2) THERE IS A HAND WRITTEN INDICATION THAT THE |
| OCCUPANCY IS "BETWEEN FIRE WALLS". THERE ARE NO |
| INDICATIONS ON THE PLAN SET DRAWINGS OR LISTING |
| CALL-OUTS THAT THE EXISTING WALLS ARE FIRE RATED. |
| |
| WHAT IS THE SEPARATION CLASSIFICATION OF THE |
| SURROUNDING OCCUPANCIES? A 2 HOUR RATING IS REQUIRED. |
| |
| PER NFPA 101, CHAPTER 6 |
| |
| 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE |
| THE |
| OCCUPANCIES ARE INTERMINGLED. |
| 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| WHERE THE |
| OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCE?RATED |
| ASSEMBLIES. |
| 6.1.14.3 MIXED OCCUPANCIES. |
| 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| CLASSIFIED AS TO ITS USE IN |
| ACCORDANCE WITH SECTION 6.1. |
| 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| RESTRICTIVE |
| REQUIREMENTS OF THE OCCUPANCIES INVOLVED, UNLESS |
| SEPARATE SAFEGUARDS |
| ARE APPROVED. |
| 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.) |
| 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, |
| EACH PART OF THE |
| BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED |
| IN THIS CHAPTER, |
| SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY |
| FIRE-RESISTIVE |
| ASSEMBLIES, AS SPECIFIED IN 6.1.14.4.2, 6.1.14.4.3, |
| TABLE 6.1.14.4.1(A), |
| AND TABLE 6.1.14.4.1(B), UNLESS SEPARATION IS PROVIDED |
| BY APPROVED |
| EXISTING SEPARATIONS OR AS OTHERWISE PERMITTED BY |
| 6.1.14.4.6. |
| 6.1.14.4.2 OCCUPANCY SEPARATIONS SHALL BE CLASSIFIED AS |
| 3-HOUR FIRE |
| RESISTANCE?RATED, 2-HOUR FIRE RESISTANCE?RATED, OR |
| 1-HOUR FIRE |
| RESISTANCE?RATED AND SHALL MEET THE REQUIREMENTS OF |
| CHAPTER 8. |
| 6.1.14.4.3 THE MINIMUM FIRE RESISTANCE RATING SPECIFIED |
| IN TABLE |
| 6.1.14.4.1(A) AND TABLE 6.1.14.4.1(B) SHALL BE |
| PERMITTED TO BE |
| REDUCED BY 1 HOUR, BUT IN NO CASE SHALL IT BE REDUCED |
| TO LESS THAN 1 |
| HOUR, WHERE THE BUILDING IS PROTECTED THROUGHOUT BY AN |
| APPROVED |
| AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH |
| 9.7.1.1(1) AND |
| SUPERVISED IN ACCORDANCE WITH 9.7.2, UNLESS PROHIBITED |
| BY THE |
| DOUBLE-DAGGER FOOTNOTE ENTRIES IN THE TABLES. |
| 6.1.14.4.4 OCCUPANCY SEPARATIONS SHALL BE VERTICAL, |
| HORIZONTAL, OR |
| BOTH OR, WHEN NECESSARY, OF SUCH OTHER FORM AS REQUIRED |
| TO PROVIDE |
| COMPLETE SEPARATION BETWEEN OCCUPANCY DIVISIONS IN THE |
| BUILDING. |
| 6.1.14.4.5* EACH SEPARATED PORTION OF THE BUILDING |
| SHALL COMPLY |
| WITH THE REQUIREMENTS FOR THE OCCUPANCY THEREIN. |
| |
| PLEASE PROVIDE SPECIFIC DETAILS OF THE SEPARATIONS AND |
| FIRE RATING OR JUSTIFY WITH SPECIFIC FIRE CODE |
| REFERENCES. |
| |
| |
| |
| 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |