Plan Review Notes
Plan Review Notes For Permit 18050851
Permit Number 18050851
Review Stop B
Sequence Number 1
Notes
Date Text
2018-06-16 16:00:05****CORRECTIONS****
 REVISED 6/20/18
 REVISED 6/28/18
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED
 SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 2. PROVIDE INFORMATION ABOUT THE PREVIOUS PERMITTED
 OCCUPANCY; IS THIS A CHANGE OF OCCUPANCY? IF YES,
 REVISE PLAN TO SHOW COMPLIANCE WITH FBC EB CHAPTER 10.
  
 3. THIS PROPERTY HAS A NUMBER OF EXPIRED PERMITS;
 PLEASE RESOLVE AT THIS TIME. AS DISCUSSED, AT LEAST
 THREE OF THE PERMITS WERE FOR THE SUBJECT UNIT. THERE
 IS AN EXPIRED ELECTRICAL PERMIT WHICH FAILED
 INSPECTION.
  
 4. PLAN SHOW OCCUPANCY AS "WAREHOUSE" WITH 500 SF PER
 PERSON, BUT THE PLAN ALSO STATES THAT THIS IS A
 "SHOWROOM". A SHOWROOM IS MERCANTILE FBC B 309.1, 60 SF
 PER PERSON, FBC B 1004.
  
 5. PROVIDE A DETAIL FOR THE BREAK ROOM SINK, FBC A
 212.3, 606.
  
 6. PLAN STATES THAT ADA BATHROOM IS "EXISTING", BUT THE
 DETAILS ARE STANDARD DETAILS. PROVIDE DETAILS OF THE
 EXISTING TO SHOW COMPLIANCE, FBC 107.
  
 7. PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF
 RECORD, FBC 107.
  
 8. DOES THIS SPACE HAVE AN ACCESSIBLE ROUTE, FROM
 ACCESSIBLE PARKING TO THE ENTRANCE? FBC A 202.4. REVISE
 PLAN TO SHOW COMPLIANCE.
  
 9. REVISED 6/28/18 PURSUANT TO MEETING WITH DOUG
 HARVEY, ABO, RICHARD COHEN ATTY, & OWNER
  
 THIS BUILDING HAS A NUMBER OF EXPIRED PERMITS. AS
 DISCUSSED, INCORPORATE THE PERMITS WHICH AFFECT THIS
 UNIT INTO THIS PERMIT:
  
 05011183, CUT WALL AND INSTALL GARAGE DOOR 9'X8'
 06082252, TAKE DOWN WALL IN BAY 2-3 AND BUILD FIRE
 RATED WALL
 06082253, ELECTRICAL FOR 06082252
  
 THIS PERMIT WILL BE ISSUED WITH PROVISO; RESOLUTION OF
 EXPIRED ELECTRICAL PERMIT 08070213 REQUIRED PRIOR TO
 FINAL INSPECTION.
  
 10. (NEW 6/28) THE PLAN INDICATES "EXISTING FIRE
 WALLS". PLEASE SEE EXPIRED PERMITS 06082252, 10070718.
 AS FINAL INSPECTIONS WERE NOT OBTAINED, THE WALLS ARE
 NOT CONSIDERED "EXISTING". THIS WORK SHOULD BE
 INCORPORATED INTO THIS PERMIT.
  
 11. (NEW 6/28) PROVIDE INFORMATION TO SHOW COMPLIANCE
 WITH FBC B TABLE 506.2. IS THE BUILDING SPRINKLERED?
 WHAT IS THE BUILDING TYPE?
  
  
  
  
  
  
  