2018-05-25 10:56:20 | PERMIT # 18050840 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | FAILED COMMENT: | | | | PROVIDE HYDRAULIC CALCULATIONS SUPPORTING THE USE OF | | THE FLEXIBLE SPRINKLER DROPS AND THE ADDITIONAL | | FRICTION LOSS ASSOCIATED WITH THESE PRODUCTS. | | | | PROVIDE A FLEXIBLE DROP DETAIL INDICATING THE MAXIMUM | | NUMBER OF BENDS PERMITTED AND THE MINIMUM BEND RADIUS | | PERMITTED IN THE LISTING DATA. | | | | SUBMIT PRODUCT DATA FOR THE FLEXIBLE SPRINKLER DROPS | | PROPOSED TO BE INSTALLED. INDICATE IF THE DROPS ARE | | BRAIDED OR UNBRAIDED. | | | | INDICATE THE MAXIMUM LENGTH OF FLEXIBLE DROP TO BE | | USED. | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | [email protected] | | |
|