Plan Review Notes For Permit 18050832 |
Permit Number |
18050832 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-05-31 15:04:52 | THIS PLAN WAS REVIEWED AND PASSED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING PROVISO COMMENTS: | | | | | | 1) THERE ARE NO INDICATIONS ON THE PLANS OF HOW THE | | EXIT PATH FROM THE EXIT DOORS WILL BE PROTECTED DURING | | DEMOLITION. | | | | PER NFPA 101 | | | | CJHAPTER 4 GENERAL | | | | 4.6.10 CONSTRUCTION, REPAIR, AND IMPROVEMENT | | OPERATIONS. | | | | 4.6.10.1* BUILDINGS, OR PORTIONS OF BUILDINGS, SHALL BE | | PERMITTED | | TO BE OCCUPIED DURING CONSTRUCTION, REPAIR, | | ALTERATIONS, OR | | ADDITIONS ONLY WHERE REQUIRED MEANS OF EGRESS AND | | REQUIRED | | FIRE PROTECTION FEATURES ARE IN PLACE AND CONTINUOUSLY | | MAINTAINED | | FOR THE PORTION OCCUPIED OR WHERE ALTERNATIVE LIFE | | SAFETY | | MEASURES ACCEPTABLE TO THE AUTHORITY HAVING | | JURISDICTION ARE IN | | PLACE. | | 4.6.10.2* IN BUILDINGS UNDER CONSTRUCTION, ADEQUATE | | ESCAPE FACILITIES | | SHALL BE MAINTAINED AT ALL TIMES FOR THE USE OF | | CONSTRUCTION | | WORKERS. ESCAPE FACILITIES SHALL CONSIST OF DOORS, | | WALKWAYS, STAIRS, | | RAMPS, FIRE ESCAPES, LADDERS, OR OTHER APPROVED MEANS | | OR DEVICES | | ARRANGED IN ACCORDANCE WITH THE GENERAL PRINCIPLES OF | | THE CODE | | INSOFAR AS THEY CAN REASONABLY BE APPLIED TO BUILDINGS | | UNDER CONSTRUCTION. | | | | PLEASE ENSURE THE AREA IS PROTECTED. | | | | | | 2) SHEET B1.02 - THERE ARE INDICATIONS OR REVISIONS TO | | THE FIRE DOORS. | | | | THIS IS A DEMO PERMIT. IF THERE ARE REVISIONS TO AN | | EXISTING PERMIT ANY REVISIONS SHALL BE SUBMITTED UNDER | | THAT PREVIOUSLY APPROVED MASTER PERMIT NUMBER WITH ALL | | REVISIONS CLOUDED FOR CLARITY. | | | | PLEASE REVIEW AND SUBMIT ANY REVISIONS UNDER THE | | MASTER. | | | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|