Plan Review Notes
Plan Review Notes For Permit 18050823
Permit Number 18050823
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-05-25 08:43:38THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) THERE IS NO GATE INDICATED ON THE PLAN.
  
 A GATE IS REQUIRED FOR FD EMERGENCY ACCESS AND 20' IN
 THE MINIMUM CLEARANCE OF A FIRE LANE.
  
 PER NFPA 241 SAFEGUARDING CONSTRUCTION AND ALTERATION
 OPERATIONS
  
 7.5.5 ACCESS ROADWAYS.
  
 7.5.5.1 EVERY BUILDING SHALL BE ACCESSIBLE BY FIRE
 DEPARTMENT
 APPARATUS BY MEANS OF ROADWAYS HAVING AN ALL-WEATHER
 DRIVING
 SURFACE OF NOT LESS THAN 6.1 M (20 FT) OF UNOBSTRUCTED
 WIDTH, HAVING
 THE ABILITY TO WITHSTAND THE LIVE LOADS OF FIRE
 APPARATUS, AND
 HAVING A MINIMUM OF 4.1 M (13 FT 6 IN.) OF VERTICAL
 CLEARANCE.
  
 7.5.5.2 ACCESS FOR USE OF FIRE DEPARTMENT APPARATUS
 SHALL BE
 PROVIDED TO THE IMMEDIATE JOB SITE AT THE START OF THE
 PROJECT
 AND MAINTAINED UNTIL COMPLETION.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  