2018-05-29 09:15:25BUILDING PLAN REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. AN EIGHT FOOT BARRIER WITH COVERED WALKWAY IS
 REQUIRED ALONG THE LENGTH OF THE BUILDING FACING 18TH
 STREET PER FBC TABLE 3306.1.
 PROTECTION OF PEDESTRIANS TABLE 3306.1
 HEIGHT OF CONSTRUCTION
 DISTANCE FROM CONSTRUCTION TO LOT LINE TYPE OF
 PROTECTION REQUIRED
 BLDG. HEIGHT - 8 FEET OR LESS
 DISTANCE TO PROPERTY LINE - LESS THAN 5 FEET REQUIRED
 PROTECTION - CONSTRUCTION RAILINGS
 - 5 FEET OR MORE - NONE
 BLDG HEIGHT - MORE THAN 8 FEET
 DISTANCE TO PROPERTY LINE - LESS THAN 5 FEET REQUIRED
 PROTECTION - BARRIER AND COVERED WALKWAY
 5 FEET OR MORE, BUT NOT MORE THAN ONE-FOURTH THE HEIGHT
 OF CONSTRUCTION - BARRIER AND COVERED WALKWAY
 5 FEET OR MORE, BUT BETWEEN ONE-FOURTH AND ONE-HALF THE
 HEIGHT OF CONSTRUCTION - BARRIER
 5 FEET OR MORE, BUT EXCEEDING ONE-HALF THE HEIGHT OF
 CONSTRUCTION - NONE
  
 2. AN ENGINEERING PERMIT AND REVIEW WILL BE REQUIRED
 FOR WORK IN A PUBLIC WAY.
 IF SCAFFOLDING OR COVERED WALKWAY EXTENDS BEYOND THE
 PRIVATE PROPERTY AND ONTO CITY RIGHT OF WAY,
 ENGINEERING WILL REQUIRE RIGHT OF WAY PERMITS. PLEASE
 CONTACT MANNY GONZALEZ AT THE ENGINEERING DEPARTMENT ?
 (561) 494-1085.
  
 3. THERE IS A DESCREPENCY BETWEEN THE SITE PLAN
 SUBMITTED FOR REVIEW AND THE SURVEY PROVIDED BY PM
 SURVEYING. THE SITE PLAN SHOWS A 15 FOOT ALLEY WITH A 5
 FOOT EASEMENT. THE SURVEY SHOWS A 10 FOOT ALLEY WITH
 THE CONSTRUCTION FENCE LOCATED ON THE PROPERTY LINE.
 CLRIFICATION IS REQUIRED BETWEEN THESE TWO DOCUMENTS.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL.
  
 4. IF THE CONSTRUCTION FENCE WILL BE LOCATED ON THE
 WEST PROPERTY LINE AND ENCROACHES AN EASEMENT, PROVIDE
 THE REQUIRED UTILITY RELEASES.
 3308.2 UTILITY FIXTURES.
 BUILDING MATERIALS, FENCES, SHEDS OR ANY OBSTRUCTION OF
 ANY KIND SHALL NOT BE PLACED SO AS TO OBSTRUCT FREE
 APPROACH TO ANY FIRE HYDRANT, FIRE DEPARTMENT
 CONNECTION, UTILITY POLE, MANHOLE, FIRE ALARM BOX OR
 CATCH BASIN, OR SO AS TO INTERFERE WITH THE PASSAGE OF
 WATER IN THE GUTTER. PROTECTION AGAINST DAMAGE SHALL BE
 PROVIDED TO SUCH UTILITY FIXTURES DURING THE PROGRESS
 OF THE WORK, BUT SIGHT OF THEM SHALL NOT BE OBSTRUCTED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  
  
  
  
  
  
  
  
  
  