Plan Review Notes
Plan Review Notes For Permit 18050811
Permit Number 18050811
Review Stop G
Sequence Number 3
Notes
Date Text
2018-07-11 06:37:211) THERE ARE TWO DIFFERENT GAS DRAWINGS SUBMITTED IN
 THIS PACKAGE. REMOVE ALL OLD DRAWINGS/DOCUMENTS AND
 COMPILE THE DOCUMENTS INTO TWO COMPLETE SETS OF PLANS
 FOR REVIEW. WPB AMEND. TO FBC SEC.107.1. 2ND REQUEST.
 2) THE EXHAUST VENT FROM THE GENERATOR SHALL BE LOCATED
 A MINIMUM OF 10 FEET FROM DOORS, WINDOWS OR OTHER
 BUILDING OPENINGS. THE SURVEY SHOWS 5 FEET. 2017
 FBC-MECH. SEC.501.3.1 & MANUF. INSTALLATION MANUAL.3RD
 REQUEST.
 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE LOW PRESSURE GAS SYSTEM OR PLACE A
 NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH SIZING
 TABLE(S) FROM THE GAS CODE OR OTHER STANDARD THAT WERE
 USED IN THE DESIGN OF THIS GAS SYSTEM. REFER TO THE
 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. 2ND
 REQUEST.
 4) INDICATE THE ORIFICE SIZE ON THE REGULATOR SPECS SO
 THE ALLOWABLE BTU LOAD OF THE REGULATOR CAN BE CHECKED
 AGAINST THE BTU LOAD OF THE APPLIANCE/EQUIPMENT
 CONNECTED.2ND REQUEST.
 5) THE NEW GAS DRAWING SHOWS AN EXISTING GAS METER AND
 THE SURVEY SHOWS A NEW GAS METER. WHICH IS IT? EXISTING
 CITY RECORDS DO NOT SHOW ANY PREVIOUS GAS SYSTEM AT
 THIS ADDRESS. CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW