2018-07-11 06:37:21 | 1) THERE ARE TWO DIFFERENT GAS DRAWINGS SUBMITTED IN | | THIS PACKAGE. REMOVE ALL OLD DRAWINGS/DOCUMENTS AND | | COMPILE THE DOCUMENTS INTO TWO COMPLETE SETS OF PLANS | | FOR REVIEW. WPB AMEND. TO FBC SEC.107.1. 2ND REQUEST. | | 2) THE EXHAUST VENT FROM THE GENERATOR SHALL BE LOCATED | | A MINIMUM OF 10 FEET FROM DOORS, WINDOWS OR OTHER | | BUILDING OPENINGS. THE SURVEY SHOWS 5 FEET. 2017 | | FBC-MECH. SEC.501.3.1 & MANUF. INSTALLATION MANUAL.3RD | | REQUEST. | | 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES | | USED TO SIZE THE LOW PRESSURE GAS SYSTEM OR PLACE A | | NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH SIZING | | TABLE(S) FROM THE GAS CODE OR OTHER STANDARD THAT WERE | | USED IN THE DESIGN OF THIS GAS SYSTEM. REFER TO THE | | 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES | | 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC. | | G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3. 2ND | | REQUEST. | | 4) INDICATE THE ORIFICE SIZE ON THE REGULATOR SPECS SO | | THE ALLOWABLE BTU LOAD OF THE REGULATOR CAN BE CHECKED | | AGAINST THE BTU LOAD OF THE APPLIANCE/EQUIPMENT | | CONNECTED.2ND REQUEST. | | 5) THE NEW GAS DRAWING SHOWS AN EXISTING GAS METER AND | | THE SURVEY SHOWS A NEW GAS METER. WHICH IS IT? EXISTING | | CITY RECORDS DO NOT SHOW ANY PREVIOUS GAS SYSTEM AT | | THIS ADDRESS. CLARIFY. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|