Plan Review Notes
Plan Review Notes For Permit 18050811
Permit Number 18050811
Review Stop G
Sequence Number 2
Notes
Date Text
2018-06-19 06:33:171) THERE ARE TWO DIFFERENT GAS DRAWINGS SUBMITTED IN
 THIS PACKAGE. REMOVE ALL OLD DRAWINGS/DOCUMENTS AND
 COMPILE THE DOCUMENTS INTO TWO COMPLETE SETS OF PLANS
 FOR REVIEW. WPB AMEND. TO FBC SEC.107.1.
 2) THE EXHAUST VENT FROM THE GENERATOR SHALL BE LOCATED
 A MINIMUM OF 10 FEET FROM DOORS, WINDOWS OR OTHER
 BUILDING OPENINGS. THE SURVEY SHOWS 5 FEET. 2017
 FBC-MECH. SEC.501.3.1 & MANUF. INSTALLATION MANUAL.
 3) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE LOW PRESSURE GAS SYSTEM OR PLACE A
 NOTE ON THE PLANS/DRAWINGS SPECIFYING WHICH SIZING
 TABLE(S) FROM THE GAS CODE OR OTHER STANDARD THAT WERE
 USED IN THE DESIGN OF THIS GAS SYSTEM. REFER TO THE
 2017 FBC-FUEL GAS SECS. 401.4, 401.8, 402.3, AND TABLES
 402.4 (1) THRU 402.4 (37) OR 2017 FBC-RES. SEC.
 G2413.3, G2412.8, G2413.1, G2413.2, & G2413.3.
 4) INDICATE THE ORIFICE SIZE ON THE REGULATOR SPECS SO
 THE ALLOWABLE BTU LOAD OF THE REGULATOR CAN BE CHECKED
 AGAINST THE BTU LOAD OF THE APPLIANCE/EQUIPMENT
 CONNECTED.
  