Plan Review Notes For Permit 18050811 |
Permit Number |
18050811 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-05-31 06:26:45 | 1) SUBMIT 2 COPIES OF SIZING TABLES FROM THE 2017 | | FBC-FUEL GAS CODE FOR THE GAS SYSTEM THAT ARE LEGIBLE. | | DO NOT TRY TO ENLARGE THIS TABLES AS THEY BECOME | | BLURRED. THESE COPIES WERE NOT ACCEPTABLE IN THE PAST | | AND ARE NOT ACCEPTABLE NOW.WPB AMEND. TO FBC SEC. | | 107.2.1. | | 2) SUBMIT TWO COPIES OF THE SIZING TABLE FROM THE 2017 | | FBC-FUEL GAS CODE BEING USED FOR THE LOW PRESSURE | | SYSTEM.2017 FBC-FUEL GAS SEC.402.1,402.3. | | 3) THE EXHAUST VENT FROM THE GENERATOR SHALL BE LOCATED | | A MINIMUM OF 10 FEET FROM DOORS, WINDOWS OR OTHER | | BUILDING OPENINGS. 2017 FBC-MECH. SEC.501.3.1. | | 4) THE GAS DRAWINGS WERE PREPARED BY DIG-IT UNLIMITED. | | IF YOU ARE GOING TO USE THESE PLANS REMOVE ALL NOTES | | FROM THE GAS PLAN THAT REFERENCE DIG-IT UNLIMITED. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | | | | | | | | | |
|