Plan Review Notes
Plan Review Notes For Permit 18050811
Permit Number 18050811
Review Stop G
Sequence Number 1
Notes
Date Text
2018-05-31 06:26:451) SUBMIT 2 COPIES OF SIZING TABLES FROM THE 2017
 FBC-FUEL GAS CODE FOR THE GAS SYSTEM THAT ARE LEGIBLE.
 DO NOT TRY TO ENLARGE THIS TABLES AS THEY BECOME
 BLURRED. THESE COPIES WERE NOT ACCEPTABLE IN THE PAST
 AND ARE NOT ACCEPTABLE NOW.WPB AMEND. TO FBC SEC.
 107.2.1.
 2) SUBMIT TWO COPIES OF THE SIZING TABLE FROM THE 2017
 FBC-FUEL GAS CODE BEING USED FOR THE LOW PRESSURE
 SYSTEM.2017 FBC-FUEL GAS SEC.402.1,402.3.
 3) THE EXHAUST VENT FROM THE GENERATOR SHALL BE LOCATED
 A MINIMUM OF 10 FEET FROM DOORS, WINDOWS OR OTHER
 BUILDING OPENINGS. 2017 FBC-MECH. SEC.501.3.1.
 4) THE GAS DRAWINGS WERE PREPARED BY DIG-IT UNLIMITED.
 IF YOU ARE GOING TO USE THESE PLANS REMOVE ALL NOTES
 FROM THE GAS PLAN THAT REFERENCE DIG-IT UNLIMITED.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
  
  
  
  
  