Plan Review Notes For Permit 18050783 |
Permit Number |
18050783 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-05-25 10:48:38 | PERMIT # 18050783 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | APPROVED PROVISO AND WITH COMMENTS: | | | | 1) THE ACTIVITY AREA MAY REQUIRE ADDITIONAL | | NOTIFICATION DEVICES. ADEQUATE COVERAGE WILL BE | | VERIFIED IN THE FIELD AT TIME OF INSPECTION. | | PLEASE REVIEW AND ADDRESS PRIOR TO INSPECTION, TO AVOID | | DELAYS IN COMPLETION. | | | | 2) THIS BUILDING IS ALREADY EQUIPPED WITH A FIRE ALARM | | SYSTEM. THE NOTIFICATION DEVICES WITHIN THIS SUITE MUST | | BE INTERCONNECTED WITH THE BUILDING'S FIRE ALARM SYSTEM | | AND VICE-VERSA. | | (I.E. IF THE NOTIFICATION DEVICES WITHIN THE SUITE ARE | | ACTIVATED, THE NOTIFICATION DEVICES THROUGHOUT THE | | BUILDING SHALL ALSO ACTIVATE. IF THE BUILDING'S | | NOTIFICATION DEVICES ARE ACTIVATED, THE DEVICES WITHIN | | THIS SUITE SHALL ALSO ACTIVATE.) | | | | FAILURE TO COMPLY WITH THE REQUIREMENTS ABOVE, SHALL | | RESULT IN A FAILED FIRE ALARM TEST INSPECTION. | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | [email protected] | | |
|