 REVIEW COMMENTS - FIRE DEPARTMENT
  
 APPROVED PROVISO AND WITH COMMENTS:
  
 1) THE ACTIVITY AREA MAY REQUIRE ADDITIONAL
 NOTIFICATION DEVICES. ADEQUATE COVERAGE WILL BE
 VERIFIED IN THE FIELD AT TIME OF INSPECTION.
 PLEASE REVIEW AND ADDRESS PRIOR TO INSPECTION, TO AVOID
 DELAYS IN COMPLETION.
  
 2) THIS BUILDING IS ALREADY EQUIPPED WITH A FIRE ALARM
 SYSTEM. THE NOTIFICATION DEVICES WITHIN THIS SUITE MUST
 BE INTERCONNECTED WITH THE BUILDING'S FIRE ALARM SYSTEM
 AND VICE-VERSA.
 (I.E. IF THE NOTIFICATION DEVICES WITHIN THE SUITE ARE
 ACTIVATED, THE NOTIFICATION DEVICES THROUGHOUT THE
 BUILDING SHALL ALSO ACTIVATE. IF THE BUILDING'S
 NOTIFICATION DEVICES ARE ACTIVATED, THE DEVICES WITHIN
 THIS SUITE SHALL ALSO ACTIVATE.)
  
 FAILURE TO COMPLY WITH THE REQUIREMENTS ABOVE, SHALL
 RESULT IN A FAILED FIRE ALARM TEST INSPECTION.
  