2018-05-17 06:39:1305/17/2018 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH
 COMMENTS NOTE - A COMPREHENSIVE REVIEW COULD NOT BE
 DONE AT THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED UPON THE RE-REVIEW OF SUBMITTED
 CORRECTIONS.
  
 1. THIS BACKFLOW IS NOT A LEAD-FREE DEVICE WHICH IS
 REQUIRED BY THE CITY OF WEST PALM BEACH UTILITY
 DEPARTMENT. YOU CAN REFER TO THEIR CROSS CONNECTION
 MANUAL IN THE CITY WEB SITE HTTP://WPB.ORG/DEPARTMENTS/
 PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BACKFLOW-CROSS-CONN
 ECTION-CONTROL-MANUAL FOR MORE INFORMATION. THE 975XL
 WATKINS MODEL IS NOT LEAD-FREE AS THE 975XL2 IS SO
 PLEASE RESUBMIT SPECS FOR IT.
 2. THE BACKFLOW MUST BE CERTIFIED BY UTILITIES PRIOR TO
 FINAL INSPECTION. PLEASE CONTACT CITY OF WPB UTILITIES
 AT 561-822-2240 FOR FURTHER DIRECTIONS.
 3. A SITE PLAN DEPICTING THE GENERAL LOCATION OF THE
 PROPOSED BACKFLOW PREVENTION DEVICE, THIS CAN BE DONE
 BY GOING TO THE PROPERTY APPRAISER WEBSITE AND PRINT
 OUT A STRUCTURAL LAYOUT OF THE BUILDING AND HAND DRAW
 THE METER LOCATION WITH THE BACKFLOW.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW