2018-05-17 06:32:01 | 05/17/2018 1ST BACKFLOW REVIEW **DENIED** WITH COMMENTS | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. THIS BACKFLOW IS NOT A LEAD-FREE DEVICE WHICH IS | | REQUIRED BY THE CITY OF WEST PALM BEACH UTILITY | | DEPARTMENT. YOU CAN REFER TO THEIR CROSS CONNECTION | | MANUAL IN THE CITY WEB SITE HTTP://WPB.ORG/DEPARTMENTS/ | | PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BACKFLOW-CROSS-CONN | | ECTION-CONTROL-MANUAL FOR MORE INFORMATION. THE 975XL | | WATKINS MODEL IS NOT LEAD-FREE AS THE 975XL2 IS SO | | PLEASE RESUBMIT SPECS FOR IT. | | 2. THE BACKFLOW MUST BE CERTIFIED BY UTILITIES PRIOR TO | | FINAL INSPECTION. PLEASE CONTACT CITY OF WPB UTILITIES | | AT 561-822-2240 FOR FURTHER DIRECTIONS. | | 3. A SITE PLAN DEPICTING THE GENERAL LOCATION OF THE | | PROPOSED BACKFLOW PREVENTION DEVICE, THIS CAN BE DONE | | BY GOING TO THE PROPERTY APPRAISER WEBSITE AND PRINT | | OUT A STRUCTURAL LAYOUT OF THE BUILDING AND HAND DRAW | | THE METER LOCATION WITH THE BACKFLOW. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | [email protected] | | 561-805-6720 | | |
|