Plan Review Notes
Plan Review Notes For Permit 18050698
Permit Number 18050698
Review Stop B
Sequence Number 1
Notes
Date Text
2018-06-20 16:08:55****CORRECTIONS****
 W.P.B. PERMIT: 18050698
  
 STEVEN KENNEDY
 ASSISTANT BUILDING OFFICIAL
 [email protected]
 561-805-6710
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1.[FBC 109]IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY
 IS REQUIRED. THE PLANS ARE TO BE STAMPED AND THE
 RECEIPT SHOWING THAT FEES DUE, IF APPLICABLE, PROVIDED.
 AFTER ALL OTHER REVIEWS HAVE PASSED, CHECK OUT ONE SET
 OF PLANS TO TAKE TO THE COUNTY.
 561-233-5025 FOR MORE INFORMATION
  
 2..[FBC 107.3.4.1] PRODUCT APPROVALS TO BE REVIEWED BY
 DESIGNER OF RECORD:
 A) PROVIDE ROOFING PRODUCT SUBMITTTAL.
 B) FOR DOOR PRODUCT FL 12509.3 PROVIDE THE DBPR COVER
 SHEET AND COPIES PRINTED AT THE CORRECT SIZE.
 C) PROVIDE AN INSTALLATION SCHEDULE OR OTHERWIZE
 SPECIFY THE CONNECTOR TO BE USED FOR THE SHUTTER
 PRODUCT NOA 17-0118.07.
  
 3.[FBC 109.3]PROVIDE COPY OF PROPOSAL WITH CONTRACTOR
 TO SHOW WORK VALUE EQUAL TO $45,000.00, OR ADJUST VALUE
 TO MATCH ACTUAL COST OF WORK. PLEASE ADJUST FEE AT
 FRONT DESK AND PAY ADJUSTED PERMIT REVIEW FEE AT TIME
 OF RE-SUBMITTAL.
  
 4.[FBC R301]PROVIDE SURVEY OF PROPERTY. SURVEY TO
 INCLUDE SLAB ELEVATION AND SHOW POSITIVE DRAINAGE FROM
 FOUNDATION.
 [FBC 110.7] PROVIDE PROFESSIONALLY PREPARED DRAINAGE
 PLAN.
  
 5.[FBC E505]SHEET A-2 REFERENCES LEVEL 2 ALTERATION.
 THIS WOULD BE LEVEL 3 ALTERATION DUE TO MORE THAN 50%
 OF EXISTING BUILDING AREA INCORPORATED INTO THE WORK
 PROPOSED.
  
 6.[FBC 107]PROVIDE DEMO PLAN TO SHOW EXISTING TO BE
 REMOVED.
  
 7.[FBC R310.2.1]SHEET A-1 WINDOW G DOESN'T MEET EGRESS
 REQUIREMENTS. IT APPEARS TO BE 36"X60" IN ELEVATION
 VIEW, BUT THE TABLE STATES IT IS 24"X48".
 ALTERNATIVELY, DEMONSTRATE COMPLIANCE WITH FBCEB 702.5.
  
 8.[FBC R608.8(2)]SHEET A-1 WINDOWS IN ELEVATION APPEAR
 TO GO ABOVE BOTTOM OF BEAM. CO-ORDINATE WINDOWS WITH
 BEAM AND ADD BEAM SCHEDULE TO SHOW WHAT IS PROVIDED
 ABOVE WINDOWS AND DOORS. PROVIDE LINTEL SCHEDULE IF
 APPLICABLE.
  
 9.[FBC R802.10.1]SHEET A-1 ADD ROOF PITCH TO ELEVATION
 AND ELEVATION CALL OUTS AS APPLICABLE FOR BEAM LOCATES
 AND WINDOW SILL HEIGHTS.
  
 10.[FBC R301.2(2)]SHEET A-1 PROVIDE CONNECTION DETAIL
 FOR DECORATIVE TRELLIS AT ENTRY FEATURE.
  
 11.[FBC 301.1]SHEET A-1 ADD DETAIL CALL OUTS AS
 APPLICABLE.
  
 12.[FBC R319]SHEET A-1 ADD NOTE FOR SITE ADDRESS.
  
 13.[FBC E907]SHEET A-2 NOTE 16 WHERE COLUMNS, SLAB AND
 BEAM MEETS EXISTING. SHOW DETAILS/NOTES OF HOW NEW WORK
 TIES INTO EXISTING STRUCTURE AT THE SLAB, COLUMN AND
 BEAM.
  
 14.[FBC 301.2.1]SHEET A-2 PRESSURES SHOWN IN ELEVATIONS
 DON'T MATCH THE PRESSURES IN THE TABLE. ALSO, THE TABLE
 SHOWS PRODUCT APPROVAL PRESSURES THAT DON'T MATCH THE
 PRODUST APPROVALS PROVIDED.
  
 15.[FBC 301.2.1]SHEET A-2 PROVIDE WINDOW LABELS IN PLAN
 VIEW TO MATCH WHAT IS SHOWN IN ELEVATION. ONE LABEL H
 IS SHOWN, BUT IT WOULD NOT BE THE CORRECT LOCATION FOR
 WINDOW BEING CALLED OUT.
  
 16.[FBC R305]SHEET A-2 PROVIDE CEILING HEIGHTS FOR ALL
 ROOMS.
  
 17.[FBC R807]SHEET A-2, S-2 SHOW LOCATION AND SIZE OF
 ATTIC ACCESS.
  
 18.[FBC R302.11]SHEET A-3 ADD FIREBLOCKING TO DETAIL ON
 TYPICAL WALL SECTION AS SHOWN IN FRONT PORCH SECTION.
  
 19.[FBC R301.1]SHEET A-3 DETAIL OF TYPICAL WALL SECTION
 SHOW 16" U-BLOCK, BUT THE NOTE CALLS OUT 8"X8" BEAM
 WITH TWO #5 BARS. SHOW ACTUAL CONDITION TO MATCH BEAM
 SCHEDULE AND SHOW REINFORCING BARS IN SECTION. ALSO,
 CALL OUT STANDARD HOOKS FOR REBAR GOING INTO FOOTERS
 AND BEAMS.
  
 20.[FBC R311.3.1]SHEET S-1 EGRESS LANDING SHALL NOT BE
 LESS THAN 1 1/2" LOWER THAN THE TOP OF THRESHOLD.
  
 21.[FBC R806]SHEET S-2 PROVIDE ROOF VENTILATION
 CALCULATION.
  
 22.[FBC E907]SHEET S-2 UPDATE NOTE #2 TO STATE 2017 FBC
 6TH EDITION.
 UPDATE STRUCTURAL NOTES CONCRETE STRENGHT TO MATCH WHAT
 IS CALLED OUT ONFOUNDATION PLANS. FIX NOTES BETWEEN
 SLUMP TEST AND REINFORCED MASONRY (OVERLAPPING TEXT).
  
 23.[FBC TABLE R301.7]SHEET S-2 ADD ALLOWABLE DEFLECTION
 L/240 FOR CEILINGS.
  
 24. ENERGY SUBMITTAL TO BE SIGNED AT OWNER/AGENT
 SIGNATURE LINE.
  
 25. [FBC 107.3.4.2] DEFERRED SUBMITTALS: IT IS PRESUMED
 THE ROOF TRUSS PACKAGE WILL BE DEFERRED. PLEASE
 ACKNOWLEGE.
  
 NOTE:
 ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF ADDITIONAL MATERIALS REQUESTED.
  
  
  
  