Plan Review Notes For Permit 18050633 |
Permit Number |
18050633 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-06-07 14:24:41 | 06/07/2018 1ST PLUMBING REVIEW**DENIED** | | | | 1) PROVIDE AN EXISTING FLOOR PLAN. FBC 107.2.1 | | | | 2) PROVIDE MAKE UP AIR CALCULATIONS FOR THE DRYER. FBC | | R G2407.1 | | | | 3) CABANA BATH HAVE AN AAV ON ITS OWN BUILDING DRAIN IS | | NOT PERMITTED AND SHALL HAVE 1 VENT THAT ENTENDS | | THROUGH THE ROOF. FBC R P3102.1 | | | | TIM HUNT | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | 561-805-6695 | | [email protected] | | |
|