Plan Review Notes
Plan Review Notes For Permit 18050633
Permit Number 18050633
Review Stop P
Sequence Number 1
Notes
Date Text
2018-06-07 14:24:4106/07/2018 1ST PLUMBING REVIEW**DENIED**
  
 1) PROVIDE AN EXISTING FLOOR PLAN. FBC 107.2.1
  
 2) PROVIDE MAKE UP AIR CALCULATIONS FOR THE DRYER. FBC
 R G2407.1
  
 3) CABANA BATH HAVE AN AAV ON ITS OWN BUILDING DRAIN IS
 NOT PERMITTED AND SHALL HAVE 1 VENT THAT ENTENDS
 THROUGH THE ROOF. FBC R P3102.1
  
 TIM HUNT
 PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER