Plan Review Notes
Plan Review Notes For Permit 18050622
Permit Number 18050622
Review Stop E
Sequence Number 1
Notes
Date Text
2018-05-23 06:27:14 
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. #12AWG FOR AN APPROX 300FT RUN IS INSUFFICIENT FOR
 ALLOWABLE VOLTAGE DROP. INDICATE VOLTAGE DROP
 COMPLIANCE WITH FBC ENERGY CONSERVATION. PROVIDE
 CORRECTIONS TO WIRE SIZE/PANEL SCHEDULE AND VOLTAGE
 DROP CALCULATION AS PER FBC EC C405.7.3 NEC 210.10(A1)
 I.N. #4
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  