1 |
|
Notes |
Date |
Text |
2018-05-23 06:27:14 | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. #12AWG FOR AN APPROX 300FT RUN IS INSUFFICIENT FOR | | ALLOWABLE VOLTAGE DROP. INDICATE VOLTAGE DROP | | COMPLIANCE WITH FBC ENERGY CONSERVATION. PROVIDE | | CORRECTIONS TO WIRE SIZE/PANEL SCHEDULE AND VOLTAGE | | DROP CALCULATION AS PER FBC EC C405.7.3 NEC 210.10(A1) | | I.N. #4 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 | | 5TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION | | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WPB | | [email protected] | | CELL: 561-657-1653 | | |
|