Plan Review Notes
Plan Review Notes For Permit 18050588
Permit Number 18050588
Review Stop P
Sequence Number 1
Notes
Date Text
2018-06-07 15:57:4506/07/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A SEPARATE PERMIT SHALL BE REQUIRED FOR IRRIGATION
 SYSTEM AND A BACKFLOW DEVICE, THE POTABLE WATER SUPPLY
 TO LAWN IRRIGATION SYSTEMS SHALL BE PROTECTED AGAINST
 BACKFLOW BY AN ATMOSPHERIC VACUUM BREAKER, A PRESSURE
 VACUUM BREAKER ASSEMBLY OR A REDUCED PRESSURE PRINCIPLE
 BACKFLOW PREVENTION ASSEMBLY. VALVES SHALL NOT BE
 INSTALLED DOWNSTREAM FROM AN ATMOSPHERIC VACUUM
 BREAKER. WHERE CHEMICALS ARE INTRODUCED INTO THE
 SYSTEM, THE POTABLE WATER SUPPLY SHALL BE PROTECTED
 AGAINST BACKFLOW BY A REDUCED PRESSURE PRINCIPLE
 BACKFLOW PREVENTION ASSEMBLY. 2017 FBC R2902.5.3 LAWN
 IRRIGATION SYSTEMS.
  
 2. POWER BATH WATER CLOSET NEEDS TO BE VENTED BY LAB
 WHICH IS ON TRUNK LINE. 2017 FBC R3101.2.1 VENTING
 REQUIRED.
  
 3. THE 4? PVC GOING TO SECOND FLOOR IS NOT REQUIRED PER
 CODE AND MAY BE TOO LARGE TO RUN IN TRUSSES. THE CODE
 WILL ALLOW A 3? PIPE BE USED PLEASE REFER TO P3004.1
 DWV SYSTEM LOAD.
  
 4. WATER HEATER PAN TERMINATION ON DRAIN PAN SHALL
 TERMINATE OUTSIDE BUILDING AND RELIEF SHALL TERMINATE
 IN PAN ON PAGE P001, 2017 FBC R 2801.6.2
  
 5. BACKFLOW PREVENTER DEVICE SHALL BE MIN 5? FROM METER
 PER UTILITIES DEPARTMENT AND PLEASE VISIT CITY OF WEST
 PALM BEACH UTILITY DEPARTMENT. YOU CAN REFER TO THEIR
 CROSS CONNECTION MANUAL IN THE CITY WEB SITE HTTP://WPB
 .ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BA
 CKFLOW-CROSS-CONNECTION-CONTROL-MANUAL FOR MORE
 INFORMATION.
  
 6. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A
 WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS
 OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN
 ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB
 AND WHIRLPOOL BATHTUB VALVES. THIS VALVE IF REQUIRED
 HAS TO BE ACCESSIBLE LOCATION LIKE UNDER A CABINET OR A
 WALL PANEL.
  
 7. WATER HEATER EF 0.92 ON A 50 GALLON OF FORM
 R405-2017 IS NOT CORRECT ACCORDING TO NEACA HOT WATER
 REGULATION 2015 AND IT SHOULD BE AT EF 0.95, PLEASE
 VISIT HTTP://WWW.CASHACME.COM/RESOURCES/NAECA-2015-REGU
 LATIONS/ FOR FURTHER DETAILS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW