2018-06-07 15:57:45 | 06/07/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. A SEPARATE PERMIT SHALL BE REQUIRED FOR IRRIGATION |
| SYSTEM AND A BACKFLOW DEVICE, THE POTABLE WATER SUPPLY |
| TO LAWN IRRIGATION SYSTEMS SHALL BE PROTECTED AGAINST |
| BACKFLOW BY AN ATMOSPHERIC VACUUM BREAKER, A PRESSURE |
| VACUUM BREAKER ASSEMBLY OR A REDUCED PRESSURE PRINCIPLE |
| BACKFLOW PREVENTION ASSEMBLY. VALVES SHALL NOT BE |
| INSTALLED DOWNSTREAM FROM AN ATMOSPHERIC VACUUM |
| BREAKER. WHERE CHEMICALS ARE INTRODUCED INTO THE |
| SYSTEM, THE POTABLE WATER SUPPLY SHALL BE PROTECTED |
| AGAINST BACKFLOW BY A REDUCED PRESSURE PRINCIPLE |
| BACKFLOW PREVENTION ASSEMBLY. 2017 FBC R2902.5.3 LAWN |
| IRRIGATION SYSTEMS. |
| |
| 2. POWER BATH WATER CLOSET NEEDS TO BE VENTED BY LAB |
| WHICH IS ON TRUNK LINE. 2017 FBC R3101.2.1 VENTING |
| REQUIRED. |
| |
| 3. THE 4? PVC GOING TO SECOND FLOOR IS NOT REQUIRED PER |
| CODE AND MAY BE TOO LARGE TO RUN IN TRUSSES. THE CODE |
| WILL ALLOW A 3? PIPE BE USED PLEASE REFER TO P3004.1 |
| DWV SYSTEM LOAD. |
| |
| 4. WATER HEATER PAN TERMINATION ON DRAIN PAN SHALL |
| TERMINATE OUTSIDE BUILDING AND RELIEF SHALL TERMINATE |
| IN PAN ON PAGE P001, 2017 FBC R 2801.6.2 |
| |
| 5. BACKFLOW PREVENTER DEVICE SHALL BE MIN 5? FROM METER |
| PER UTILITIES DEPARTMENT AND PLEASE VISIT CITY OF WEST |
| PALM BEACH UTILITY DEPARTMENT. YOU CAN REFER TO THEIR |
| CROSS CONNECTION MANUAL IN THE CITY WEB SITE HTTP://WPB |
| .ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICATIONS/BA |
| CKFLOW-CROSS-CONNECTION-CONTROL-MANUAL FOR MORE |
| INFORMATION. |
| |
| 6. ROMAN TUB STANDALONE REQUIRED A CONTROL VALVE BY A |
| WATER TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B125.3, EXCEPT WHERE SUCH PROTECTION IS |
| OTHERWISE PROVIDED BY A COMBINATION TUB/SHOWER VALVE IN |
| ACCORDANCE WITH SECTION P2708.4. FBC R 2713.3 BATHTUB |
| AND WHIRLPOOL BATHTUB VALVES. THIS VALVE IF REQUIRED |
| HAS TO BE ACCESSIBLE LOCATION LIKE UNDER A CABINET OR A |
| WALL PANEL. |
| |
| 7. WATER HEATER EF 0.92 ON A 50 GALLON OF FORM |
| R405-2017 IS NOT CORRECT ACCORDING TO NEACA HOT WATER |
| REGULATION 2015 AND IT SHOULD BE AT EF 0.95, PLEASE |
| VISIT HTTP://WWW.CASHACME.COM/RESOURCES/NAECA-2015-REGU |
| LATIONS/ FOR FURTHER DETAILS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |