2018-05-19 06:25:03 | 1) SUBMIT A FLOOR PLAN OF THE PROPOSED TOILET ROOM |
| SHOWING THE LENGTH AND WIDTH DIMENSIONS OF THE TOILET |
| ROOM. |
| 2) SHOW THE REQUIRED FIXTURE CLEARANCES FOR THE |
| PLUMBING FIXTURES. COMPLY WITH 2017 FBCR SECS R307, |
| .P2705. SHOW THE REQUIRED CLEARANCE IN FRONT OF THE |
| WATER CLOSET AND LAVATORY. |
| 3) IT APPEARS FROM THE PLANS YOU ARE RUNNING A SEPARATE |
| BULDING DRAIN FOR THIS HALF BATH AND CONNECTING TO THE |
| MAIN SEWER ON THE EXTERIOR. IF THAT IS THE CASE, YOU |
| CANNOT USE AN AIR ADMITTANCE VALE FOR THIS |
| INSTALLATIONPER MANFACTURER'S INSTALLATION |
| REQUIREMENTS. EACH BUILSING DRAIN/BUILDING SEWER SHALL |
| HAVE ONE VENT TO THE ATMOSPHERE. |
| 4) SHOW THE DOOR SWING ON THE HALF BATH. THE LOCATION |
| OF DOORS SHALL NOT INTERFERE WITH THE OPERATION OF |
| DOORS OR WINDOWS. 2017 FBCR SEC.P2705. |
| 5) BATHROOMS AND OTHER SIMILAR ROOMS SHALL BE PROVIDED |
| WITH LIGHT AND VENTILATION COMPLYING WITH 2017 FBCR |
| SEC. R303.3, M1507. |
| 6) THIS TYPE OF ALTERATION TRIGGERS THE REQUIREMENT FOR |
| SMOKE ALARMS IN THE DWELLING UNIT PER THE 2017 FBCR |
| SEC.R314.2.2. |
| 7) SUBMIT A COMPLETE SET OF PLANS (ELECTRICAL, |
| MECHANICAL, BUILDING) FOR THE ENTIRE SCOPE OF WORK TO |
| BE DONE.WPB AMEND. TO FBC SECS.107.3.5, 107.3.5.3. - |
| MINIMUM REQUIREMENTS FOR PLAN REVIEW. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |
| 561-805-6692 |
| |