Plan Review Notes For Permit 18050522
Permit Number 18050522
Review Stop P
Sequence Number 1
Notes
Date Text
2018-05-19 06:25:031) SUBMIT A FLOOR PLAN OF THE PROPOSED TOILET ROOM
 SHOWING THE LENGTH AND WIDTH DIMENSIONS OF THE TOILET
 ROOM.
 2) SHOW THE REQUIRED FIXTURE CLEARANCES FOR THE
 PLUMBING FIXTURES. COMPLY WITH 2017 FBCR SECS R307,
 .P2705. SHOW THE REQUIRED CLEARANCE IN FRONT OF THE
 WATER CLOSET AND LAVATORY.
 3) IT APPEARS FROM THE PLANS YOU ARE RUNNING A SEPARATE
 BULDING DRAIN FOR THIS HALF BATH AND CONNECTING TO THE
 MAIN SEWER ON THE EXTERIOR. IF THAT IS THE CASE, YOU
 CANNOT USE AN AIR ADMITTANCE VALE FOR THIS
 INSTALLATIONPER MANFACTURER'S INSTALLATION
 REQUIREMENTS. EACH BUILSING DRAIN/BUILDING SEWER SHALL
 HAVE ONE VENT TO THE ATMOSPHERE.
 4) SHOW THE DOOR SWING ON THE HALF BATH. THE LOCATION
 OF DOORS SHALL NOT INTERFERE WITH THE OPERATION OF
 DOORS OR WINDOWS. 2017 FBCR SEC.P2705.
 5) BATHROOMS AND OTHER SIMILAR ROOMS SHALL BE PROVIDED
 WITH LIGHT AND VENTILATION COMPLYING WITH 2017 FBCR
 SEC. R303.3, M1507.
 6) THIS TYPE OF ALTERATION TRIGGERS THE REQUIREMENT FOR
 SMOKE ALARMS IN THE DWELLING UNIT PER THE 2017 FBCR
 SEC.R314.2.2.
 7) SUBMIT A COMPLETE SET OF PLANS (ELECTRICAL,
 MECHANICAL, BUILDING) FOR THE ENTIRE SCOPE OF WORK TO
 BE DONE.WPB AMEND. TO FBC SECS.107.3.5, 107.3.5.3. -
 MINIMUM REQUIREMENTS FOR PLAN REVIEW.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW