2018-05-15 17:25:451ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18050464
 5/15/18
  
 CODES IN EFFECT:
 FBC BC- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC MC- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC RE- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC-SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1: REFER TO SECTION 1609.1.1 FBC BC AND
 PROVIDE THE WIND LOAD DESIGN CRITERIA IN ACCORDANCE
 WITH ASCE 7-2010 INCLUDING ULTIMATE WINDSPEED, EXPOSURE
 CATEGORY, IMPORTANCE FACTOR, AND DESIGN PRESSURES-
 LATERAL AND UPLIFT. INDICATE HOW THE FAT BOY CLIP WILL
 BE ATTACHED TO THE CONDENSER AND TO THE STAND, AND
 SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE NOA.
  
 2) M-2: PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE NEW
 AHU'S. SHOW THE PIPING RUNS AND DISCHARGE LOCATIONS.
  
 3) M-2: PROVIDE AUTOMATICALLY CONTROLLED SHUTOFF
 DAMPERS FOR THE O/A INTAKE DUCTS- SECTION C403.2.4.3
 FBC-17 ENERGY CONSERVATION.THE DAMPERS SHALL BE EITHER
 MOTORIZED OR GRAVITY TYPE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
  