2018-05-15 13:44:42 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| |
| 1) THERE IS NO INDICATION OF COMPLIANCE WITH THE |
| CURRENT EDITION OF THE FLORIDA FIRE PREVENTION CODE. |
| |
| THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| APPLICABLE CODES OR STANDARDS. |
| |
| THERE DOES NOT APPEAR TO BE ANY CONFLICT; HOWEVER, |
| PLEASE TAKE NOTE AND ENSURE COMPLIANCE AS THAT IS HOW |
| IT WILL BE INSPECTED BY FIRE INSPECTORS. |
| |
| |
| |
| 2) SHEET E 1 - THERE IS AN EXIT SIGN INDICATED AT THE |
| END OF THE REAR CORRIDOR LEADING INTO A CONFERNECE |
| ROOM. FROM THE CONFERNECE ROOM THERE IS A DOOR LEADING |
| TO THE WAREHOUSE AND AN EXIT FROM THE WAREHOUSE. |
| |
| THE OCCUPANCY CAN SUUPORT THE ONE EXIT AT THE FRONT, |
| BUT THE EXIT SIGN AT THE CONFERENCE ROOM DOOR NEEDS TO |
| BE MOVE TO INSIDE THE CONFERENCE ROOM LEADING TO THE |
| CORRIDOR. |
| |
| THE WAREHOUSE EXIT SIGN CAN STAD ALONE FROM THAT AREA. |
| |
| PER NFPA 101, CHAPTER 38 NEW BUSINESS |
| |
| 38.2 MEANS OF EGRESS REQUIREMENTS. |
| 38.2.1 GENERAL. |
| 38.2.1.1 ALL MEANS OF EGRESS SHALL BE IN ACCORDANCE |
| WITH CHAPTER 7 AND |
| THIS CHAPTER. |
| |
| 38.2.4.3 A SINGLE EXIT SHALL BE PERMITTED FOR A ROOM OR |
| AREA WITH A TOTAL |
| OCCUPANT LOAD OF LESS THAN 100 PERSONS, PROVIDED THAT |
| ALL OF THE |
| FOLLOWING CRITERIA ARE MET: |
| (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE AT |
| THE LEVEL OF EXIT |
| DISCHARGE FOR THE BUILDING. |
| (2) THE TOTAL DISTANCE OF TRAVEL FROM ANY POINT, |
| INCLUDING TRAVEL WITHIN |
| THE EXIT, SHALL NOT EXCEED 100 FT (30 M). |
| (3) THE TOTAL DISTANCE OF TRAVEL SPECIFIED IN |
| 38.2.4.3(2) SHALL BE ON THE |
| SAME STORY, OR, IF TRAVERSING OF STAIRS IS NECESSARY, |
| SUCH STAIRS SHALL |
| NOT EXCEED 15 FT (4570 MM) IN HEIGHT, AND BOTH OF THE |
| FOLLOWING |
| ALSO SHALL APPLY: |
| (A) INTERIOR STAIRS SHALL BE PROVIDED WITH COMPLETE |
| ENCLOSURES TO |
| SEPARATE THEM FROM ANY OTHER PART OF THE BUILDING, WITH |
| NO |
| DOOR OPENINGS THEREIN. |
| (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2 |
| SHALL BE |
| PERMITTED TO SERVE ALL STORIES PERMITTED WITHIN THE 15 |
| FT (4570 |
| MM) VERTICAL TRAVEL LIMITATION |
| |
| PER NFPA 101, CHAPTER 7 MEANS OF EGRESS. |
| |
| 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE |
| PERMITTED TO BE |
| THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS, |
| PROVIDED THAT SUCH |
| ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED. |
| FOYERS, LOBBIES, AND |
| RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS |
| SHALL NOT BE |
| CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE |
| ARRANGED SO |
| THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA |
| IDENTIFIED UNDER |
| PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43. |
| |
| PLEASE CHANGE THE LOCATION OF THE REAR EXIT SIGN. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |