Plan Review Notes
Plan Review Notes For Permit 18050464
Permit Number 18050464
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-05-15 13:44:42THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THERE IS NO INDICATION OF COMPLIANCE WITH THE
 CURRENT EDITION OF THE FLORIDA FIRE PREVENTION CODE.
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 THERE DOES NOT APPEAR TO BE ANY CONFLICT; HOWEVER,
 PLEASE TAKE NOTE AND ENSURE COMPLIANCE AS THAT IS HOW
 IT WILL BE INSPECTED BY FIRE INSPECTORS.
  
  
  
 2) SHEET E 1 - THERE IS AN EXIT SIGN INDICATED AT THE
 END OF THE REAR CORRIDOR LEADING INTO A CONFERNECE
 ROOM. FROM THE CONFERNECE ROOM THERE IS A DOOR LEADING
 TO THE WAREHOUSE AND AN EXIT FROM THE WAREHOUSE.
  
 THE OCCUPANCY CAN SUUPORT THE ONE EXIT AT THE FRONT,
 BUT THE EXIT SIGN AT THE CONFERENCE ROOM DOOR NEEDS TO
 BE MOVE TO INSIDE THE CONFERENCE ROOM LEADING TO THE
 CORRIDOR.
  
 THE WAREHOUSE EXIT SIGN CAN STAD ALONE FROM THAT AREA.
  
 PER NFPA 101, CHAPTER 38 NEW BUSINESS
  
 38.2 MEANS OF EGRESS REQUIREMENTS.
 38.2.1 GENERAL.
 38.2.1.1 ALL MEANS OF EGRESS SHALL BE IN ACCORDANCE
 WITH CHAPTER 7 AND
 THIS CHAPTER.
  
 38.2.4.3 A SINGLE EXIT SHALL BE PERMITTED FOR A ROOM OR
 AREA WITH A TOTAL
 OCCUPANT LOAD OF LESS THAN 100 PERSONS, PROVIDED THAT
 ALL OF THE
 FOLLOWING CRITERIA ARE MET:
 (1) THE EXIT SHALL DISCHARGE DIRECTLY TO THE OUTSIDE AT
 THE LEVEL OF EXIT
 DISCHARGE FOR THE BUILDING.
 (2) THE TOTAL DISTANCE OF TRAVEL FROM ANY POINT,
 INCLUDING TRAVEL WITHIN
 THE EXIT, SHALL NOT EXCEED 100 FT (30 M).
 (3) THE TOTAL DISTANCE OF TRAVEL SPECIFIED IN
 38.2.4.3(2) SHALL BE ON THE
 SAME STORY, OR, IF TRAVERSING OF STAIRS IS NECESSARY,
 SUCH STAIRS SHALL
 NOT EXCEED 15 FT (4570 MM) IN HEIGHT, AND BOTH OF THE
 FOLLOWING
 ALSO SHALL APPLY:
 (A) INTERIOR STAIRS SHALL BE PROVIDED WITH COMPLETE
 ENCLOSURES TO
 SEPARATE THEM FROM ANY OTHER PART OF THE BUILDING, WITH
 NO
 DOOR OPENINGS THEREIN.
 (B) A SINGLE OUTSIDE STAIR IN ACCORDANCE WITH 7.2.2
 SHALL BE
 PERMITTED TO SERVE ALL STORIES PERMITTED WITHIN THE 15
 FT (4570
 MM) VERTICAL TRAVEL LIMITATION
  
 PER NFPA 101, CHAPTER 7 MEANS OF EGRESS.
  
 7.5.1.6 EXIT ACCESS FROM ROOMS OR SPACES SHALL BE
 PERMITTED TO BE
 THROUGH ADJOINING OR INTERVENING ROOMS OR AREAS,
 PROVIDED THAT SUCH
 ROOMS OR AREAS ARE ACCESSORY TO THE AREA SERVED.
 FOYERS, LOBBIES, AND
 RECEPTION ROOMS CONSTRUCTED AS REQUIRED FOR CORRIDORS
 SHALL NOT BE
 CONSTRUED AS INTERVENING ROOMS. EXIT ACCESS SHALL BE
 ARRANGED SO
 THAT IT IS NOT NECESSARY TO PASS THROUGH ANY AREA
 IDENTIFIED UNDER
 PROTECTION FROM HAZARDS IN CHAPTERS 11 THROUGH 43.
  
 PLEASE CHANGE THE LOCATION OF THE REAR EXIT SIGN.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  