2018-05-20 14:10:26 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PANEL SCHEDULE PROVIDED ONLY SHOWS LOADS FOR 2 OF |
| THE PHASES OF A 3 PHASE SYSTEM. PROVIDE A 3 PHASE |
| PANELS SCHEDULE DETAILING THE LOAD FOR EACH PHASE TO |
| CONFIRM THAT THE PANEL IS NOT OVERLOADED. SEE COMMENT |
| #2 FOR WATER HEATER. ADDITIONALLY, ASSUMED LOADS CANNOT |
| BE ACCEPTED. THIS PANEL IS CLOSE TO BEING OVERLOADED, |
| PROVIDE ACCURATE LOAD CALCULATION. NEC 215.5, 408.4, |
| 408.30; WPB FBC 107.2.1 |
| 2. PANEL SCHEDULE SHOWS A SR-20L WATER HEATER ON A 208 |
| VOLT CIRCUIT. THE MANUFACTURERS SPEC SHEET FOR THIS |
| UNIT STATES THAT IT DRAWS 4160 WATTS, NOT 2400 AS SHOWN |
| IN PANEL SCHEDULE. CLARIFY AND/OR CORRECT. NEC 110.3; |
| WPB FBC 107.2.1 |
| 3. PROVIDE GFCI PROTECTION FOR DRINKING FOUNTAIN. THE |
| GFCI DEVICE MUST BE READILY ACCESSIBLE. NEC 422.5, |
| 422.52 |
| 4. PROVIDE CHART OF INTERIOR LIGHTING POWER ALLOWANCES |
| EXPRESSED IN WATTAGE PER THE FBC ENERGY CODE IN |
| RELATION TO THE WATTAGE OF THE CONNECTED INTERIOR |
| LIGHTING PROPOSED TO COMPLY WITH CODE. FBC EC C405.4.2 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |