Plan Review Notes For Permit 18050464 |
Permit Number |
18050464 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-05-27 19:21:44 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED | | SETS OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PAGES VOID AS | | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE | | NEED "VOID", RENDERING THEM NOT USABLE. | | | | 2. FBC B 1609, THIS PARCEL IS LOCATED IN EXPOSURE C, | | REVISE DESIGN CRITERIA AND PRESSURES ACCORDINGLY. | | | | 3. FBC 107, ENERGY CALC INPUT DATA IS INCOMPLETE; NO | | FENESTRATION SHOWN. REVISE OR CLARIFY. CHECK ALL. | | |
|