Plan Review Notes
Plan Review Notes For Permit 18050423
Permit Number 18050423
Review Stop P
Sequence Number 1
Notes
Date Text
2018-05-17 07:28:4905/17/2018 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH
 COMMENTS NOTE - A COMPREHENSIVE REVIEW COULD NOT BE
 DONE AT THIS TIME AND ADDITIONAL PLAN REVIEW COMMENTS
 MAY BE GENERATED UPON THE RE-REVIEW OF SUBMITTED
 CORRECTIONS.
  
 1. THIS BACKFLOW IS NOT IN A LOCATION WHICH IS REQUIRED
 BY THE CITY OF WEST PALM BEACH UTILITY DEPARTMENT. YOU
 CAN REFER TO THEIR CROSS CONNECTION MANUAL IN THE CITY
 WEB SITE HTTP://WPB.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FO
 RMS-PUBLICATIONS/BACKFLOW-CROSS-CONNECTION-CONTROL-MANU
 AL FOR MORE INFORMATION. PLEASE CALL UTILITIES FOR
 FURTHER INFORMATION AS TO THE APPROVAL LOCATION OF THIS
 DEVICE 561-822-4440.
 2. THE BACKFLOW MUST BE CERTIFIED BY UTILITIES PRIOR TO
 FINAL INSPECTION. PLEASE CONTACT CITY OF WPB UTILITIES
 AT 561-822-2240 FOR FURTHER DIRECTIONS.
 3. A SITE PLAN DEPICTING THE GENERAL LOCATION OF THE
 PROPOSED BACKFLOW PREVENTION DEVICE, THIS CAN BE DONE
 BY GOING TO THE PROPERTY APPRAISER WEBSITE AND PRINT
 OUT A STRUCTURAL LAYOUT OF THE BUILDING AND HAND DRAW
 THE METER LOCATION WITH THE BACKFLOW.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW