2018-05-14 05:52:12 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE ACCURATE RISER DIAGRAM OF EXISTING SERVICE. |
| NEC 215.5; WPB FBC 107.2.1 |
| |
| 2. (4), 750MCM IN A 5'' CONDUIT CAN'T SUPPORT AN 800AMP |
| SERVICE AS SHOWN IN EXISTING RISER DIAGRAM. NEC 230.31, |
| NEC 310.15B16 |
| |
| 3. MARK OCP FOR EXISTING PANEL "A" IN MDP ON EXISTING |
| RISER DIAGRAM. |
| |
| 4. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED |
| CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS, |
| AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY |
| WITH CODE. NEC 210.8, 210.12, 215.5, 408.4; WPB FBC |
| 107.3.5; FBC RE E3706.2, E3902 |
| |
| 5. TRIANGLE NOTE #2 IN ELECTRICAL LEGEND STATES |
| (ELECTRICAL PANEL), THE NOTE IS ON THE PLAN SEVERAL |
| TIMES IN MULTIPLE LOCATIONS. PLEASE CORRECT. |
| |
| 6. VALUE OF WORK TOO LOW. PROVIDE COPY OF SIGNED |
| CONTRACT (BY OWNER AND ELECTICAL COMPANY) WITH SCOPE |
| AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. |
| FBC 109.3 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| |