2018-05-15 19:03:38 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT TWO SETS OF FLOOR PLANS OF THE ENTIRE CONDO | | UNIT AND INDICATE THE BATHROOM THAT IS TO BE REMODELED. | | PROVIDE A DIMENSIONED LAYOUT PLAN OF THE BATHROOM AND | | THE SHOWER STALL. FBC 107.2.1 | | | | 2) FBC 107.2.1 - INFORMATION ON CONSTRUCTION DOCUMENTS. | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE OF | | THE PERSON RESPONSIBLE FOR THE DESIGN. | | | | 3) THE GLAZING IN THE SHOWER ENCLOSURE IS REQUIRED TO | | BE SAFETY GLAZING COMPLYING WITH FBC 2406.1. |
|