2018-07-30 14:25:05 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18050313 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC EB = FBC EXISTING BUILDING |
| FBC R = FBC RESIDENTIAL |
| |
| 1. OK. |
| |
| 2. WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE |
| NOTE PAGE 13 OF 20, FACTORS APPLY DEPENDING ON |
| SUBSTRATE, EDGE DISTANCE AND FASTENER. FOR FASTENER, IF |
| USING TAPCON, BE SPECIFIC AS TO WHICH TAPCON (TAPCON |
| W/ADVANCED THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR). |
| 2.1. THE EDGE DISTANCE DOESN'T MEET THE TABLE ON PAGE |
| 13 OF 20. |
| IF YOU USE ALL POINT ANCHORS AS SPECIFIED THAN YOUR |
| MINIMUM EDGE DISTANCE WOULD BE 3.5" AND YOU WOULD USE |
| FACTOR .78*10(ANCHOR SPACING) FOR A NEW ANCHOR SPACING |
| OF 7.8". |
| PLEASE LOOK AT THIS TABLE EDGE DISTANCE VS. SPACING |
| SCHEDULE FOR ANCHORS AND CHOOSE THE ANCHOR AND SPACING |
| THAT WORKS BEST FOR YOUR PROJECT. |
| CALL IF ANY QUESTIONS ABOUT THE EDGE SPACING. |
| DYLAN BATTLES 561-805-6718. |
| |
| ALSO, THE I.D. NO. 4&5 FROM SALES SHEET DON'T MATCH THE |
| SUBMITTAL SHEET OPENING 4&5. I HAVE NO COMMENT ON THAT |
| BECAUSE IT WON'T CHANGE SPACING VALUES, BUT YOU MAY |
| WANT TO VERIFY THE SIZE BEFORE FABRICATION. |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |