2019-03-21 13:59:37 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 3RD REVIEW |
| PLUMBING COMMEMTS: DENIED |
| 1. RE: A-0.0.02; REVISE FIXTURE BREAKDOWN TO REFLECT |
| 2017 FBC PL 403 AS REQUIRED BY WPB FBC 107.2.1. ARCH |
| A-0.0.02 STILL NOT CORRECTED. |
| 2. RE: A-2.0.03; ALL REFERENCE TO 2014 CODES SHALL BE |
| REVISED TO READ 2017 PER WPB FBC 107.2.1. PLUMBING |
| P0.0.00 OK; ARCH A2.0.03 STILL NOT CORRECTED. ADDED |
| 8/22//2019, PER CONVERSATION WITH STACEY, REFERENCE ON |
| A-2.0.03 WAS NOT FOUND. CORRECTION WAS MADE ON A-.0.01. |
| IF UPON REVIEW OF RESUBMITTED PLANS, THE REFERENCE IS |
| STILL FOUND WE WILL REDLINE IT ON THE PLANS TO CONFORM. |
| 3. RE: P-3.0.00; SANITARY PIPING FROM TOILET ROOM |
| TOILET BATTERY SHALL NOT DISCHARGE INTO THE COMBINATION |
| WASTE AND VENT BRANCH PER FBC PL 915.1. CONNECT AT A |
| POINT DOWNSTREAM OF THE COMBINATION WASTE AND VENT |
| BRANCH. P-1.3.1.01 FLOOR PLAN HAS BEEN CORRECTED BUT |
| P-3.0.00 RISER DIAGRAM HAS NOT. PLEASE CORRECT PER WPB |
| FBC 107.2.1. |
| 4. RE: P-3.1.00; PER WPB FBC 107.2.1 PLEASE PROVIDE |
| CALULATIONS FOR SIZING OF GREASY WASTE SYSTEM. |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN |
| ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL |
| SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| REMAIN IN PACKAGE AND BE MARKED "VOID". |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |