2019-03-21 13:59:37CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 3RD REVIEW
 PLUMBING COMMEMTS: DENIED
 1. RE: A-0.0.02; REVISE FIXTURE BREAKDOWN TO REFLECT
 2017 FBC PL 403 AS REQUIRED BY WPB FBC 107.2.1. ARCH
 A-0.0.02 STILL NOT CORRECTED.
 2. RE: A-2.0.03; ALL REFERENCE TO 2014 CODES SHALL BE
 REVISED TO READ 2017 PER WPB FBC 107.2.1. PLUMBING
 P0.0.00 OK; ARCH A2.0.03 STILL NOT CORRECTED. ADDED
 8/22//2019, PER CONVERSATION WITH STACEY, REFERENCE ON
 A-2.0.03 WAS NOT FOUND. CORRECTION WAS MADE ON A-.0.01.
 IF UPON REVIEW OF RESUBMITTED PLANS, THE REFERENCE IS
 STILL FOUND WE WILL REDLINE IT ON THE PLANS TO CONFORM.
 3. RE: P-3.0.00; SANITARY PIPING FROM TOILET ROOM
 TOILET BATTERY SHALL NOT DISCHARGE INTO THE COMBINATION
 WASTE AND VENT BRANCH PER FBC PL 915.1. CONNECT AT A
 POINT DOWNSTREAM OF THE COMBINATION WASTE AND VENT
 BRANCH. P-1.3.1.01 FLOOR PLAN HAS BEEN CORRECTED BUT
 P-3.0.00 RISER DIAGRAM HAS NOT. PLEASE CORRECT PER WPB
 FBC 107.2.1.
 4. RE: P-3.1.00; PER WPB FBC 107.2.1 PLEASE PROVIDE
 CALULATIONS FOR SIZING OF GREASY WASTE SYSTEM.
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN
 ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL
 SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS.
 ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD
 REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715