2018-12-27 14:20:02CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2014 5TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2012
 5TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014
 5TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2014 5TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2014 5TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2014 5TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2014 5TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 2ND REVIEW
  
 PLUMBING COMMEMTS: DENIED
  
  
 1. RE: A-0.0.02; REVISE FIXTURE BREAKDOWN TO REFLECT
 2017 FBC PL 403 AS REQUIRED BY WPB FBC 107.2.1
 2. 2ND REQUEST; A-0.0.02 THE PLUMBING FIXTURE BREAKDOWN
 IS LISTED FOR THE TENNIS CLUB HOUSE PLEASE PROVIDE A
 BREAKDOWN FOR THE WATERSIDE BAR, THE POOL AND
 SURROUNDING AREA ALONG WITH A SITE PLAN THAT SHOWS THE
 OCCUPANT LOAD FOR EACH AREA. THE FIXTURE COUNT SHALL
 COMPLY WITH FBC PL TABLE 403.1 ADDITION INFORMATION
 REQUIRED PER WPB FBC 107.2.1 NOTE; ARCHITECT DID NOT
 ADDRESS CONCERNS FOR THE POOL AND SURROUNDING AREAS AS
 REQUESTED.
 3. RE: A-2.0.03; ALL REFERENCE TO 2014 CODES SHALL BE
 REVISED TO READ 2017 PER WPB FBC 107.2.1
 4. 2ND REQUEST:
 RE: P-0.0.00; THE PLUMBING SPEC UNDER THE PIPE HANGER
 SPACING SCHEDULE SHALL COMPLY WITH FBC PL TABLE 308.5.
  GIVE EXTRA CONSIDERATION TO COPPER TUBING.
 5. 2ND REQUEST: RE; P-0.0.01 + P-3.3.00 THE SCHEDULE
 FOR THE WATER HEATER, EXPANSION TANK AND RECIRCULATION
 PUMP DO NOT MATCH PLEASE CLARIFY AND PROVIDE
 MANUFACTURE SPECIFICATION. PER WPB AMEND TO FBC 107.2.1
 SEE FOLLOWING AND CLARIFY PER WPB FBC 107.2.1
 A. EXPANSION TANK P-0.0.00=ET-1, P-3.3.00 &
 P-3.4.00=EX-1.
 B. SCHEDULES FOR HOT WATER RECIRCULATING PUMP(S) ON
 P-3.4.00 AND P-0.0.00 DO NOT MATCH.
 C. SCHEDULES FOR GAS WATER HEATER ON P-3.4.00 AND
 P-0.0.00 DO NOT MATCH.
 D. SCHEDULES FOR MIXING VALVE ON P-3.4.00 AND P-0.0.00
 DO NOT MATCH.
 6. 2ND REQUEST: PLEASE SHOW TRAP PRIMERS ON THE FLOOR
 DRAIN ON THE ISOMETRIC DRAWING. PER FBC PL 1002.4.1
 IN LIEU OF SHOWING THE TRAP PRIMERS PROVIDE A NOTE ON
 P-3.0.00 RISER DIAGRAM STATING ?PROVIDE TRAP PRIMERS
 FOR ALL FLOOR DRAINS; SEE P-4.1.00, DETAILS 5 & 6?
 7. IT APPEARS THAT THE ORIGINAL DOMESTIC WATER RISER
 DIAGRAM P-3.1.00 NOW CONTAINS THE GREASY WASTE
 ISOMETRIC AND GREASE INTERCEPTOR CALCULATIONS.
 A. 2ND REQUEST: ON THE WATER ISOMETRIC PLEASE SIZE THE
 BRANCH PIPING FOR THE GANG BATHROOMS. 107.3.5.1.3(13)
 OK. SHOWN ON P-3.2.00 (SEE NOTES BELOW CONCERNING
 CONFUSION OF PDF TITLES)
 B. 2ND REQUEST; PLEASE PROVIDE PIPING DETAILS FOR THE
 WATER FILTERS BNB-2, BNB-2.1 AND 2015.1.
 107.3.5.1.3(13)
 C. 2ND REQUEST; PLEASE PROVIDE BACKFLOW DEVICES FOR THE
 WATER FILTER, ICE MACHINE, BEVERAGE DISPENSERS AND
 COFFEE MAKERS. PER FBC PL 608.3 , 608.16.1, 608.16.10
 NOTE 3 ON P-1.3.03 DOES NOT SEEM TO ADDRESS THIS ISSUE.
 D. TO SUMMARIZE, WATER RISER ISOMETRIC FOR THE PROJECT
 SHALL SHOW ALL REQUIRED VALVES, BACKFLOW PREVENTERS,
 WATER HAMMER ARRESTORS AND OTHER PERTINENT DEVICES PER
 WPB FBC 107.2.1
 ADDITIONAL COMMENTS
 1 .RE: P-3.0.00; SANITARY PIPING FROM TOILET ROOM
 TOILET BATTERY SHALL NOT DISCHARGE INTO THE COMBINATION
 WASTE AND VENT BRANCH PER FBC PL 915.1. CONNECT AT A
 POINT DOWNSTREAM OF THE COMBINATION WASTE AND VENT
 BRANCH. CORRECT ON P-1.3.01 TO REFLECT THE SAME.
 2. RE: P-0.0.01; FIXTURE SCHEDULE L-1 AND L-2, CALL FOR
 TMV PER FBC 416.5 AND SPECIFY PER WPB WPC 107.2.1
 3. RE: P-4.1.00; DETAIL FOR SENSOR FAUCET CONNECTION,
 SPECIFY TMV PER WPB WPC 107.2.1
 4. RE: P-4.0.00; DETAILS 5 & 6 FLUSHING FLOOR DRAINS.
 WHERE ARE THESE BEING USED? SHOW ON FLOOR PLAN AND
 SCHEDULE, SPECIFY CODE COMPLIANT FLUSH VALVE. IF NOT
 PART OF PROJECT THEN DELETE THE DETAILS. WPB FBC
 107.2.1
 5. RE: P-3.3.00, P-3.4.00; WATER HEATER DETAILS ARE
 CONFLICTING. RECONCILE THE DETAILS TO MATCH EACH OTHER
 PER WPB FBC 107.2.1. PLEASE NOTE THE SCHEMATIC DETAIL
 #1 ON P-3.4.00 IS CONFUSING. THE ISOMETRIC DETAIL #2 ON
 P-3.4.00 IS VERY BUSY AND THERE ARE A NUMBER OF ENDS
 THAT ARE NOT IDENTIFIED. DIFFERENT DETAILS HAVE
 DIFFERENT QUANTITIY OF HOT WATER RECIRCULATION PUMPS.
 THERE IS DIFFERENT INFO FOR EXPANSION TANK.
 THE VENTING AND COMBUSTION AIR FOR THE WATER HEATER IS
 DIFFERENT IN DIFFERENT DETAILS.
 SPECIAL NOTES:
 P-3.3.00 ENLARGED WATER HEATING SYSTEM IS ACTUALLY THE
 PLUMBING NATURAL GAS RISER DIAGRAM
 P-3.2.00 NATURAL GAS RISER DIAGRAM IS ACTUALLY THE
 PLUMBING DOMESTIC WATER RISER DIAGRAM
 P-3.1.00 PLUMBING DOMESTIC WATER RISER DIAGRAM IS
 ACTUALLY THE PLUMBING GREASE WASTE DRAINAGE RISER
 DIAGRAM
 P-3.1.01 NATURAL GAS RISER DIAGRAM IS INCOMPLETE AND
 THE CORRECTED DRAWING AND CALCULATIONS ARE ON P-3.3.00
 PLEASE CORRECT AND OR DELETE AS REQUIRED PER WPB FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715