Plan Review Notes
Plan Review Notes For Permit 18050277
Permit Number 18050277
Review Stop M
Sequence Number 2
Notes
Date Text
2018-11-26 14:42:362ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18050277
 11/26/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) A-1.0.05, A-2.0.02, A-5.0.01, A-6.0.00, & M-1.3.01:
 THE EXTERIOR DOORS AND INTERIOR DOORS ENCLOSING THE
 POOL EQUIPMENT STORAGE AND ELECTRICAL ROOMS SHALL BE
 FIRE-RATED PER SECTION 707.6 FBC B. ( CORRECTED
 ARCHITECTURAL PLANS NOW SHOW THE EXTERIOR WALLS TO BE
 3HR FIRE-RATED). FIRE DAMPERS SHALL BE PROVIDED FOR THE
 MAKEUP AIR LOUVERS ON THE EAST WALLS, AND FOR THE AC-1
 OUTDOOR AIR INTAKE LOUVER, THE FOOD PREP EXHAUST
 OUTLET, AND THE EXHAUST HOOD MAKEUP AIR INLET- SECTION
 607.5.2 FBC M.
  
 2) SHEET M-1.3.01: THE STAINLESS STEEL EXHAUST DUCKWORK
 IN THE POOL EQUIPMENT STORAGE ROOM IS NOT IN COMPLIANCE
 WITH SECTION 510.9 FBC M WHICH REQUIRES THE DUCT TO BE
 G90 GALVANIZED OR NON-METALLIC MATERIALS THAT EXHIBIT A
 FLAME SPREAD/SMOKE-DEVELOPED INDEX OF 25/50.
  
 3) M-1.3.01: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR
 EF-1 WITH AN APPROVAL STAMP BY THE ENGINEER OF RECORD.
 THE SPECS SHALL INDICATE THE FAN HAS BEEN TESTED FOR
 USE IN CONVEYING CORROSIVE OR HAZARDOUS EXHAUST FUMES-
 SECTION 304.1 FBC M. A) CLARIFY THE LOCATION OF THE
 FAN- ABOVE OR BELOW THE CEILING. IF LOCATED ABOVE THE
 CEILING PROVIDE AN ACCESS PANEL FOR SERVICE AND
 REPLACEMENT- SECTION 306.1 FBC M.
  
 4) A-2.0.02 & M-1.3.01: AS INDICATED BY NOTE #6 ON
 M-1.3.01 PLEASE SHOW THE EXACT LOCATION OF THE EF-1
 EXHAUST OUTLET TO VERIFY COMPLIANCE WITH SECTION
 501.3.1(2) FBC M. (PLEASE NOTE THIS OUTLET SHALL NOT BE
 PROTECTED WITH A FIRE DAMPER- SECTION 510.6.7 FBC M).
  
 5) M-1.3.01: COMMENT #3(E) FROM THE 1ST TREVIEW STILL
 EXISTS- PLEASE SUBMIT SPECS FOR THE CHEMICAL TANKS IN
 THE POOL EQUIPMENT STORAGE ROOM.
  
 6) COMMENT #2 FROM THE 1ST REVIEW REQUESTING EVIDENCE
 OF ENERGY EFFICIENCY COMPLIANCE WAS NOT ADDRESSED- THE
 PROPOSED BUILDING SHALL BE IN COMPLIANCE WITH THE FBC
 EC. REFER TO SECTIONS C101.2 -SCOPE AND C401.2
 APPLICATION (COMPLIANCE PATHS). PROVIDE A COMPLIANCE
 SUBMITTAL C101.5.1- COMPLIANCE MATERIALS.
  
 7) COMMENT #6 FROM THE 1ST REVIEW STILL EXISTS. IF THE
 REQUESTED WIND LOAD ENGINEERING IS TO BE A DEFERRED
 SUBMITTAL PLEASE INDICATE THAT ON THE CORRECTED PLANS,
 OR IN THE RESPONSE NARRATIVE.
  
 8) COMMENT #8 FROM THE 1ST REVIEW HAS NOT BEEN
 COMPLETELY ADDRESSED. WHEN USING A MECHANICAL
 VENTILATION SYSTEM TO PROVIDE COMBUSTION AIR, THE
 SYSTEM SHALL PROVIDE THE SPECIFIED COMBUSTION RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR- SECTION
 304.9.3 FBC FG. BASED ON THE AIR BALANCE CALCULATION ON
 M-1.3.01, IT APPEARS THAT ALL VENTILATION AIR FROM AC-1
 WILL BE UTILIZED AS MAKEUP AIR FOR THE EXHAUST SYSTEMS.
  
 9) M-1.3.01: THE LOCATION OF THE MAKEUP AIR OPENING FOR
 THE EXHAUST HOOD SHALL BE A MINIMUM 3' AWAY FROM THE
 FOOD PREP EXHAUST OUTLET- SECTION 501.3.1 (3) FBC M.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  