2018-12-27 16:14:54 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2012 |
| 5TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| 5TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2014 5TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2014 5TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2014 5TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2014 5TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 2ND REVIEW |
| |
| GAS COMMEMTS: DENIED |
| |
| 1.THERE ARE TWO GAS RISERS SHTS P-3.1.01 AND P-3.3.00 |
| PLEASE CLARIFY PER WPB FBC 107.2.1 |
| NOTE: P-3.1.01 NATURAL GAS RISER DIAGRAM IS INCOMPLETE |
| AND THE CORRECTED DRAWING WITH CALCULATIONS ARE ON |
| P-3.3.00 |
| PLEASE CORRECT AND/ OR DELETE AS REQUIRED PER WPB FBC |
| 107.2.1 |
| 2. GAS EQUIPMENT ITEMS 2013 AND 2014 SPEC SHEET MBTU |
| REQUIREMENTS ARE GREATER THAN THAT CALLED OUT ON |
| P-3.3.00. PLEASE CORRECT AS NECESSARY PER WPB FBC |
| 107.2.1 |
| PROVIDE GAS EQUIPMENT SCHEDULE LISTING ITEMS 2011 |
| THROUGH 2014 WITH DESCRIPTION , GWH-1 W/DESCRIPTION AND |
| MBTU DEMAND FOR EACH. |
| 3. SPECIFY 2ND STAGE REGULATORS COMPLYING WITH ANSI |
| Z21.80 AND CALL OUT VENT ELIMINATORS OR VENTS AS |
| REQUIRED PER WPB FBC 107.2.1. IF VENTS ARE REQUIRED |
| SHOW ROUTING, SIZING AND TERMINATION WITH DETAIL ON THE |
| PLAN PER WPB FBC 107.2.1 |
| 4. 2ND REQUEST; SUBMIT CALCULATIONS FOR COMBUSTION AIR |
| PER THE FBC FG 304.1 |
| 5. SHOW LOCATION OF DIRECT VENT AND EXHAUST VENT |
| TERMINALS WHERE THEY PENETRATE THE EXTERIOR WALL ON THE |
| PLUMBING FLOOR PLAN P-1.3.03 IN ACCORDANCE WITH FBC FG |
| 502 THROUGH 505 PER WPB FBC 107.2.1. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| |