Plan Review Notes
Plan Review Notes For Permit 18050277
Permit Number 18050277
Review Stop B
Sequence Number 2
Notes
Date Text
2019-01-14 10:10:07UPON ADDRESS ASSIGNMENT, PLEASE UPLOAD COVER SHEET WITH
 NEW ADDRESS ON IT.
  
 COMMENT BY:
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
 THE CITY OF WEST PALM BEACH
 BUILDING PLANS EXAMINER PX4191
 COMMERCIAL BUILDING INSPECTOR BN7557
  
2018-12-13 13:24:56****CORRECTIONS****
 W.P.B. PERMIT: 18050277
  
 1ST REVIEW
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 2ND REVIEW: DECEMBER 12, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. OK
  
 2 A1.0.04, HOW OCCPUANT LOAD OF 106 WAS DETERMINED IS
 NOT CLEAR.
 2ND REVIEW:
 A) 2-2 SHEET A-0.0.02 BUILDING OCCUPANY TABLE DOESN?T
 MATCH OCCUPANT LOAD TABLE 1004.1.2.
 B) REQUIRED FIXTURE TABLE STATES A-3 OCCUPANCY, BUT IT
 SHOULD BE A-2. PLEASE ADJUST TO MATCH BUILDING CODE
 DATA.
 C) OCCUPANCY USED FOR REQUIRED FIXTURES SHOULD MATCH
 THE BUILDING OCCUPANCY CURRENTLY IT SAY 166 PERSONS FOR
 PLUMBING COUNT AND 106 FOR BUILDING OCCUPANCY.
 D) THE AMOUNT OF FIXTURES PROVIDED DOESN?T MATCH WHAT
 SHOWS IN PLAN VIEW ON SHEET A-1.0.05 AND PLUMBING
 SHEETS.
 PLEASE MATCH NUMBERS OF FIXTURE PROVIDED.
 E) REVIEW BUILDING OCCUPANCY AND USE FUNCTIONS FROM
 TABLE 1004.1.2 TO DETERMINE THE OCCUPANT LOAD [FBC
 1004.6]MULTIPLE OCCUPANCIES
 EXAMPLE:
 A) 200 GROSS - KITCHENS COMMERCIAL I SEE THE INTERIOR
 COMMERCIAL KITCHEN AS APPROX. 400 SQ. PLUS THE OUTSIDE
 SERVING CAN BE INCLUDED.
 B) 300 GROSS ? STORAGE. THE SECTION BEHIND THE KITCHEN
 IS ABOUT 1574 SQ. FT
  
 C) 15 GROSS ? UNCONCENTRATED TABLES AND CHAIRS. THE
 OUTSIDE EATING CAN BE JUST THE AREA FROM BARS EDGE TO
 ROOFS EDGE.
 PLEASE UPDATE SO AREAS ARE CLEAR
 SQ. FOOTAGE UNDER AIR, SQ. FOOTAGE FOR OUTDOOR EATING
 AND TOTAL SQ. FOOTAGE.
  
 3. OK
  
 4. OK
  
 5. OK
  
 6. OK
  
 NEW COMMENTS:
 7. REMOVE SHEET AGA A-1.0.0.01 SITE PLAN SINCE SHEET
 AGA A.0.0.05 IS THE APPROVED SITE PLAN. SHEETS AGA
 A1.0.02 AND AGA A1.0.03 MAY NOT BE NEEDED IN THE SET
 EITHER.
  
 8. SHEET A-1.0.04 INFORMATION ON SHEET IS NOT SHOWING
 UP. PLEASE RE-LOAD THE SHEET WITH INTENDED CONTENT.
  
 9. [FBC ENERGY C401.2]APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING
 SECTION 9.4.1.1(G) OF THE STANDARD.
 2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
 NO ENERGY CALCULATIONS WERE FOUND IN SUPPORTING
 DOCUMENTS.
 PLEASE UPLOAD THE ENERGY CALCULATIONS (LOAD
 CALCULATIONS WERE PROVIDED)
  
 10. SOME WALLTYPES ON FLOOR PLAN A-1.0.05 DON?T MATCH
 WITH WALL TYPES LISTED ON A-6.0.00
 VERIFY ALL WALL TYPES TO MATCH
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  
  
  