Date |
Text |
2019-01-14 10:10:07 | UPON ADDRESS ASSIGNMENT, PLEASE UPLOAD COVER SHEET WITH |
| NEW ADDRESS ON IT. |
| |
| COMMENT BY: |
| DYLAN BATTLES |
| 561-805-6718 |
| [email protected] |
| |
| THE CITY OF WEST PALM BEACH |
| BUILDING PLANS EXAMINER PX4191 |
| COMMERCIAL BUILDING INSPECTOR BN7557 |
| |
2018-12-13 13:24:56 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18050277 |
| |
| 1ST REVIEW |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| 2ND REVIEW: DECEMBER 12, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC ENERGY = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. OK |
| |
| 2 A1.0.04, HOW OCCPUANT LOAD OF 106 WAS DETERMINED IS |
| NOT CLEAR. |
| 2ND REVIEW: |
| A) 2-2 SHEET A-0.0.02 BUILDING OCCUPANY TABLE DOESN?T |
| MATCH OCCUPANT LOAD TABLE 1004.1.2. |
| B) REQUIRED FIXTURE TABLE STATES A-3 OCCUPANCY, BUT IT |
| SHOULD BE A-2. PLEASE ADJUST TO MATCH BUILDING CODE |
| DATA. |
| C) OCCUPANCY USED FOR REQUIRED FIXTURES SHOULD MATCH |
| THE BUILDING OCCUPANCY CURRENTLY IT SAY 166 PERSONS FOR |
| PLUMBING COUNT AND 106 FOR BUILDING OCCUPANCY. |
| D) THE AMOUNT OF FIXTURES PROVIDED DOESN?T MATCH WHAT |
| SHOWS IN PLAN VIEW ON SHEET A-1.0.05 AND PLUMBING |
| SHEETS. |
| PLEASE MATCH NUMBERS OF FIXTURE PROVIDED. |
| E) REVIEW BUILDING OCCUPANCY AND USE FUNCTIONS FROM |
| TABLE 1004.1.2 TO DETERMINE THE OCCUPANT LOAD [FBC |
| 1004.6]MULTIPLE OCCUPANCIES |
| EXAMPLE: |
| A) 200 GROSS - KITCHENS COMMERCIAL I SEE THE INTERIOR |
| COMMERCIAL KITCHEN AS APPROX. 400 SQ. PLUS THE OUTSIDE |
| SERVING CAN BE INCLUDED. |
| B) 300 GROSS ? STORAGE. THE SECTION BEHIND THE KITCHEN |
| IS ABOUT 1574 SQ. FT |
| |
| C) 15 GROSS ? UNCONCENTRATED TABLES AND CHAIRS. THE |
| OUTSIDE EATING CAN BE JUST THE AREA FROM BARS EDGE TO |
| ROOFS EDGE. |
| PLEASE UPDATE SO AREAS ARE CLEAR |
| SQ. FOOTAGE UNDER AIR, SQ. FOOTAGE FOR OUTDOOR EATING |
| AND TOTAL SQ. FOOTAGE. |
| |
| 3. OK |
| |
| 4. OK |
| |
| 5. OK |
| |
| 6. OK |
| |
| NEW COMMENTS: |
| 7. REMOVE SHEET AGA A-1.0.0.01 SITE PLAN SINCE SHEET |
| AGA A.0.0.05 IS THE APPROVED SITE PLAN. SHEETS AGA |
| A1.0.02 AND AGA A1.0.03 MAY NOT BE NEEDED IN THE SET |
| EITHER. |
| |
| 8. SHEET A-1.0.04 INFORMATION ON SHEET IS NOT SHOWING |
| UP. PLEASE RE-LOAD THE SHEET WITH INTENDED CONTENT. |
| |
| 9. [FBC ENERGY C401.2]APPLICATION. |
| COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE |
| FOLLOWING: |
| 1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING |
| SECTION 9.4.1.1(G) OF THE STANDARD. |
| 2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN |
| ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH |
| SECTION C406 AND TENANT SPACES SHALL COMPLY WITH |
| SECTION C406.1.1. |
| 3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404, |
| C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING |
| ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT |
| OF THE STANDARD REFERENCE DESIGN BUILDING. |
| NO ENERGY CALCULATIONS WERE FOUND IN SUPPORTING |
| DOCUMENTS. |
| PLEASE UPLOAD THE ENERGY CALCULATIONS (LOAD |
| CALCULATIONS WERE PROVIDED) |
| |
| 10. SOME WALLTYPES ON FLOOR PLAN A-1.0.05 DON?T MATCH |
| WITH WALL TYPES LISTED ON A-6.0.00 |
| VERIFY ALL WALL TYPES TO MATCH |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| |
| |
| |