Plan Review Notes
Plan Review Notes For Permit 18050277
Permit Number 18050277
Review Stop P
Sequence Number 1
Notes
Date Text
2018-06-23 11:14:331ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A.0.0.02 THE PLUMBING FIXTURE BREAKDOWN IS
 LISTED FOR THE TENNIS CLUB HOUSE PLEASE PROVIDE A
 BREAKDOWN FOR THE WATERSIDE BAR, THE POOL AND
 SURROUNDING AREA ALONG WITH A SITE PLAN THAT SHOWS THE
 OCCUPANT LOAD FOR EACH AREA. THE FIXTURE COUNT SHALL
 COMPLY WITH FBC PL TABLE 403.1 ADDITION INFORMATION
 REQUIRED PER WPB AMEND TO FBC 107.2.1
  
 2. SHT. A.2.0.03 SHOW CLEAR FLOOR SPACE FOR ACCESSIBLE
 TOILETS AND SHOW DIMENSIONS ON ALL ACCESSIBLE CLEAR
 FLOOR FOR ALL FIXTURES. PER WPB AMEND TO FBC 107.2.1
 FBC ACC 604.3.1, 602.2, 605.3, 606.2
  
 3. SHT. A.7.0.01 THE DIMENSIONS ON THE DETAILS ARE
 EXTREMELY LIGHT AND HARD TO READ PLEASE DARKEN ALL
 DIMENSIONS. PER WPB AMEND TO FBC 107.2.1
  
 4. SHT. P.0.0.00 THE PLUMBING SPEC 1.2, 1.6, 4.1 SHALL
 REFLECT THE CURRENT CODE FBC PL 2017 6TH EDITION
  
 5. SHT. P.0.0.00 THE PLUMBING SPEC UNDER THE PIPE
 HANGER SPACING SCHEDULE SHALL COMPLY WITH FBC PL TABLE
 308.5
  
 6. PROVIDE A SITE PLAN SHOWING THE GREASE INTERCEPTOR
 AND PIPING DETAIL. PER WPB AMEND TO FBC 107.2.1,
 107.3.5.1.3(11)
  
 7. PROVIDE SIZING CALCULATION FOR THE GREASE
 INTERCEPTOR. PER WPB AMEND TO FBC 107.2.1,
 107.3.5.1.3(11)
  
 8. SHT. P.0.0.01 + P.3.3.00 THE SCHEDULE FOR THE WATER
 HEATER, EXPANSION TANK AND RECIRCULATION PUMP DO NOT
 MATCH PLEASE CLARIFY AND PROVIDE MANUFACTURE
 SPECIFICATION. PER WPB AMEND TO FBC 107.2.1
  
 9. SHT. P.3.3.00 DETAILS #3 + 35 APPEAR TO BE DIFFERENT
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 10. PLEASE EXPAND THE SANITARY ISOMETRIC AND SEPARATE
 THE SANITARY FROM THE GREASE. 107.3.5.1.3(13)
  
 11. PLEASE SHOW TRAP PRIMERS ON THE FLOOR DRAIN ON THE
 ISOMETRIC DRAWING. PER FBC PL 1002.4.1
  
 12. THE PLUMBING FIXTURES IN THE BAR AREA SHALL ALSO
 DISCHARGE TO THE GREASE SYSTEM. PER FBC 1003.3.1 AND
 WEST PALM BEACH, FLORIDA - CODE OF ORDINANCES SEC.
 90-125.(7) SEC. 90-126.(7)
  
 13. THE HAND SINK IN THE KITCHEN DOES NOT APPEAR TO BE
 ON THE ISOMETRIC PLEASE CLARIFY. 107.3.5.1.3(13)
  
 14. ON THE WATER ISOMETRIC PLEASE SIZE THE BRANCH
 PIPING FOR THE GANG BATHROOMS. 107.3.5.1.3(13)
  
 15. PLEASE PROVIDE PIPING DETAILS FOR THE WATER FILTERS
 BNB-2, BNB-2.1 AND 2015.1. 107.3.5.1.3(13)
  
 16. PLEASE PROVIDE BACKFLOW DEVISES FOR THE WATER
 FILTER, ICE MACHINE, BEVERAGE DISPENSERS AND COFFEE
 MAKERS. PER FBC PL 608.3 , 608.16.1, 608.16.10
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  