Plan Review Notes
Plan Review Notes For Permit 18050277
Permit Number 18050277
Review Stop M
Sequence Number 1
Notes
Date Text
2018-06-11 12:01:181ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18050277
 6/11/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SEPARATE PERMITS ARE REQUIRED FOR THE COMMERCIAL
 KITCHEN HOOD, THE FIRE SUPRESSION SYSTEM, AND THE
 WALKIN FOOD STORAGE AND KEG COOLERS. PLEASE PLACE
 ADVISORY NOTES ON THE PLANS.
  
 2) THE PROPOSED BUILDING SHALL BE IN COMPLIANCE WITH
 THE FBC EC. REFER TO SECTIONS C101.2 -SCOPE AND C401.2
 APPLICATION (COMPLIANCE PATHS). PROVIDE A COMPLIANCE
 SUBMITTAL C101.5.1- COMPLIANCE MATERIALS,
  
 2) SHEET M-1.3.01: PROVIDE EXHAUST VENTILATION
 CALCULATIONS FOR THE TOILET ROOMS, AND THE POOL
 EQUIPMENT AND CHEMICAL STORAGE ROOMS- TABLE 403.3.1 AND
 SECTION 510.2. FBC M
  
 3) M-1.3.01, POOL EQP/STORAGE ROOM: A) INDICATE HOW
 MAKEUP AIR IS BEING PROVIDED TO THE ROOM- SECTION
 510.6.5 FBC M B) CLARIFY HOW THE SYSTEM WILL OPERATE-
 CONTINUOUSLY OR INTERMITTENTLY. C) INDICATE THE TYPE OF
 EXHAUST DUCTWORK TO BE INSTALLED- SECTION 510.9. D) THE
 EXHAUST OUTLET APPEARS TO BE WITHIN 10' OF THE DOORS TO
 THE ROOM AND NOT IN COMPLIANCE WITH SECTION 501.3.1(2)
 FBC M. SHOW ALL REQUIRED CLEARANCE DISTANCE
 MEASUREMENTS ON THE PLAN. E) SUBMIT SPECIFICATIONS FOR
 THE CHEMICAL STORAGE TANKS AND EMBOLDEN THE PRINT ON
 THE TANK SYSMBOLS TO CLEARLY SHOW THE CHEMICAL NAME AND
 GALLON CONTENT- TABLE 414.2.5(1) FBC B.
  
 4) M-0.0.01: PROVIDE AIR BALANCE CALCULATIONS FOR THE
 KITCHEN- SECTION 508.1.2 FBC M
  
 5) M-1.3.01: PROVIDE A DUCT SMOKE DETECTOR ON THE
 SUPPLY TRUNK OF AC-1- SECTION 606.2.1
  
 6) M-1.3.01: PROVIDE WIND LOAD ENGINEERING FOR
 INSTALLATION OF CU-1 & CU-2- SECTION 301.15 FBC M.
  
 7) K-1.4: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL
 GAS-FIRED COOKING EQUIPMENT- SECTION 623.1 FBC FG.
  
 8) M-0.0.01: PROVIDE COMBUSTION AIR CALCULATIONS FOR
 THE GAS-FIRED COOKING APPLIANCES- SECTION 304 FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  