2018-06-11 12:01:18 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18050277 |
| 6/11/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC R- FLORIDA RESIDENTIAL CODE SIXTH EDITION 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SEPARATE PERMITS ARE REQUIRED FOR THE COMMERCIAL |
| KITCHEN HOOD, THE FIRE SUPRESSION SYSTEM, AND THE |
| WALKIN FOOD STORAGE AND KEG COOLERS. PLEASE PLACE |
| ADVISORY NOTES ON THE PLANS. |
| |
| 2) THE PROPOSED BUILDING SHALL BE IN COMPLIANCE WITH |
| THE FBC EC. REFER TO SECTIONS C101.2 -SCOPE AND C401.2 |
| APPLICATION (COMPLIANCE PATHS). PROVIDE A COMPLIANCE |
| SUBMITTAL C101.5.1- COMPLIANCE MATERIALS, |
| |
| 2) SHEET M-1.3.01: PROVIDE EXHAUST VENTILATION |
| CALCULATIONS FOR THE TOILET ROOMS, AND THE POOL |
| EQUIPMENT AND CHEMICAL STORAGE ROOMS- TABLE 403.3.1 AND |
| SECTION 510.2. FBC M |
| |
| 3) M-1.3.01, POOL EQP/STORAGE ROOM: A) INDICATE HOW |
| MAKEUP AIR IS BEING PROVIDED TO THE ROOM- SECTION |
| 510.6.5 FBC M B) CLARIFY HOW THE SYSTEM WILL OPERATE- |
| CONTINUOUSLY OR INTERMITTENTLY. C) INDICATE THE TYPE OF |
| EXHAUST DUCTWORK TO BE INSTALLED- SECTION 510.9. D) THE |
| EXHAUST OUTLET APPEARS TO BE WITHIN 10' OF THE DOORS TO |
| THE ROOM AND NOT IN COMPLIANCE WITH SECTION 501.3.1(2) |
| FBC M. SHOW ALL REQUIRED CLEARANCE DISTANCE |
| MEASUREMENTS ON THE PLAN. E) SUBMIT SPECIFICATIONS FOR |
| THE CHEMICAL STORAGE TANKS AND EMBOLDEN THE PRINT ON |
| THE TANK SYSMBOLS TO CLEARLY SHOW THE CHEMICAL NAME AND |
| GALLON CONTENT- TABLE 414.2.5(1) FBC B. |
| |
| 4) M-0.0.01: PROVIDE AIR BALANCE CALCULATIONS FOR THE |
| KITCHEN- SECTION 508.1.2 FBC M |
| |
| 5) M-1.3.01: PROVIDE A DUCT SMOKE DETECTOR ON THE |
| SUPPLY TRUNK OF AC-1- SECTION 606.2.1 |
| |
| 6) M-1.3.01: PROVIDE WIND LOAD ENGINEERING FOR |
| INSTALLATION OF CU-1 & CU-2- SECTION 301.15 FBC M. |
| |
| 7) K-1.4: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL |
| GAS-FIRED COOKING EQUIPMENT- SECTION 623.1 FBC FG. |
| |
| 8) M-0.0.01: PROVIDE COMBUSTION AIR CALCULATIONS FOR |
| THE GAS-FIRED COOKING APPLIANCES- SECTION 304 FBC FG. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |