2018-06-23 11:40:55 | 1ST REVIEW: FBC 2017 6TH EDITION |
| |
| GAS COMMENTS: |
| |
| 1. THERE ARE TWO GAS RISERS SHTS P.3.1.00 AND P.3.2.00 |
| PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 2. A LINE PRESSURE REGULATOR SHALL BE INSTALLED WHERE |
| THE APPLIANCE IS DESIGNED TO OPERATE AT A LOWER |
| PRESSURE THAN THE SUPPLY PRESSURE. LINE GAS PRESSURE |
| REGULATORS SHALL BE LISTED AS COMPLYING WITH ANSI |
| Z21.80. ACCESS SHALL BE PROVIDED TO PRESSURE |
| REGULATORS. PRESSURE REGULATORS SHALL BE PROTECTED FROM |
| PHYSICAL DAMAGE. REGULATORS INSTALLED ON THE EXTERIOR |
| OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. PLEASE SHOW ON RISER ALONG WITH SHUT OFF |
| VALVES AND SEDIMENT TRAPS. FBC FG 410.1, 408.4, 409.1 |
| |
| 3. GAS NOTE #4 STATES 3" DIRECT VENT THE RISER SHOWS 2" |
| PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR |
| 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES |
| DRYERS). |
| |
| 5. SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION, |
| SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND |
| ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL |
| GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426 |
| THROUGH G2439. |
| |
| 6. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT AND |
| REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| SEC.G2408.1. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |