Plan Review Notes
Plan Review Notes For Permit 18050277
Permit Number 18050277
Review Stop G
Sequence Number 1
Notes
Date Text
2018-06-23 11:40:551ST REVIEW: FBC 2017 6TH EDITION
  
 GAS COMMENTS:
  
 1. THERE ARE TWO GAS RISERS SHTS P.3.1.00 AND P.3.2.00
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 2. A LINE PRESSURE REGULATOR SHALL BE INSTALLED WHERE
 THE APPLIANCE IS DESIGNED TO OPERATE AT A LOWER
 PRESSURE THAN THE SUPPLY PRESSURE. LINE GAS PRESSURE
 REGULATORS SHALL BE LISTED AS COMPLYING WITH ANSI
 Z21.80. ACCESS SHALL BE PROVIDED TO PRESSURE
 REGULATORS. PRESSURE REGULATORS SHALL BE PROTECTED FROM
 PHYSICAL DAMAGE. REGULATORS INSTALLED ON THE EXTERIOR
 OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. PLEASE SHOW ON RISER ALONG WITH SHUT OFF
 VALVES AND SEDIMENT TRAPS. FBC FG 410.1, 408.4, 409.1
  
 3. GAS NOTE #4 STATES 3" DIRECT VENT THE RISER SHOWS 2"
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 4. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017
 FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR
 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES
 DRYERS).
  
 5. SUBMIT A DETAIL SHOWING THE TYPE OF VENT, LOCATION,
 SIZE, TERMINATION POINT, HEIGHT ABOVE THE ROOF AND
 ANCHORING DETAILS OF THE GAS VENT(S) PER 2017 FBC-FUEL
 GAS SECS. 502 THRU 505 OR 2017 FBC-RES. SEC.G2426
 THROUGH G2439.
  
 6. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL GAS EQUIPMENT AND
 REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  