Date |
Text |
2018-05-22 13:23:51 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET A 0.0.02 - THERE IS A NOTE, UNDER BUIOLDING |
| CODE DATA, INDICATING "TYPE VB NONSPRINKLERED" YET |
| THERE A FIRE PROTECTION DOCUMENTS SHOWING FIRE |
| SPRINKLERS. |
| |
| PLEASE CORRECT OR JUSTIFY. |
| |
| |
| |
| 2) SHEET A 0.0.02 - UNDER "PROJECTS COMPONENTS, |
| BUILDING OCCUPANCY" TABLE THERE ARE NO FIGURES ENTERED |
| INTO THE COLUMNS LABLED "FACTOR OR PERSONS". |
| |
| |
| PLEASE CORRECT |
| |
| |
| |
| 3) SHEET FP 0.0.00 - UNDER THE SECTION "FIRE PROTECTION |
| FLOW TEST DATA" THERE ARE NO FIGURES ENTERED INTO AREAS |
| INDICATED. THESE FIGURES ARE REQUIRED TO PROVIDE |
| ADAQUATE WATER SUPPLY AND SYSTEM DEMANDS. |
| |
| PLEASE CORRECT. |
| |
| |
| |
| 4) SHEET FP 0.0.00 - UNDER THE SECTION " DESIGN |
| CRITERIA" STORAGE, MECH/ELECT. ROOMS, ORDINARY HAZARD |
| GRUOP 1 IS INDICATED. HOWEVER, ON SHEET FP 1.3.01 THERE |
| ARE NO HEASD INDICATED IN THE ELECTRICAL ROOM. |
| |
| PER NFPA 13 |
| |
| 8.15.11 ELECTRICAL EQUIPMENT. |
| 8.15.11.1 UNLESS THE REQUIREMENTS OF 8.15.11.3 ARE MET, |
| SPRINKLER |
| PROTECTION SHALL BE REQUIRED IN ELECTRICAL EQUIPMENT |
| ROOMS. |
| 8.15.11.2 HOODS OR SHIELDS INSTALLED TO PROTECT |
| IMPORTANT |
| ELECTRICAL EQUIPMENT FROM SPRINKLER DISCHARGE SHALL BE |
| NONCOMBUSTIBLE. |
| 8.15.11.3 SPRINKLERS SHALL NOT BE REQUIRED IN |
| ELECTRICAL EQUIPMENT |
| ROOMS WHERE ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| (1) THE ROOM IS DEDICATED TO ELECTRICAL EQUIPMENT ONLY. |
| (2) ONLY DRY-TYPE ELECTRICAL EQUIPMENT IS USED. |
| (3) EQUIPMENT IS INSTALLED IN A 2-HOUR FIRE-RATED |
| ENCLOSURE |
| INCLUDING PROTECTION FOR PENETRATIONS. |
| (4) NO COMBUSTIBLE STORAGE IS PERMITTED TO BE STORED IN |
| THE |
| ROOM. |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY. |
| |
| |
| |
| 5) SHEET 1.3.01 - THERE APPEARS TO BE NO SPRINKLER HEAD |
| COVERAGE IN THE FRONT PORCH BAR AREA. |
| |
| PER NFPA 13 |
| |
| 8.15.1.2.18 SOFFITS, EAVES, OVERHANGS, AND DECORATIVE |
| FRAME |
| ELEMENTS. SPRINKLERS SHALL BE PERMITTED TO BE OMITTED |
| FROM |
| WITHIN COMBUSTIBLE SOFFITS, EAVES, OVERHANGS, AND |
| DECORATIVE |
| FRAME ELEMENTS THAT ARE CONSTRUCTED IN ACCORDANCE WITH |
| 8.15.1.2.18.1 THROUGH 8.15.1.2.18.4. |
| 8.15.1.2.18.1 COMBUSTIBLE SOFFITS, EAVES, OVERHANGS, |
| AND DECORATIVE |
| FRAME ELEMENTS SHALL NOT EXCEED 4 FT 0 IN. (1.2 M) IN |
| WIDTH. |
| 8.15.1.2.18.2 COMBUSTIBLE SOFFITS, EAVES, OVERHANGS, |
| AND DECORATIVE |
| FRAME ELEMENTS SHALL BE DRAFTSTOPPED, WITH A MATERIAL |
| EQUIVALENT TO THAT OF THE SOFFIT, INTO VOLUMES NOT |
| EXCEEDING 160 FT3 |
| (4.5 M3). |
| 8.15.1.2.18.3 COMBUSTIBLE SOFFITS, EAVES, OVERHANGS, |
| AND DECORATIVE |
| FRAME ELEMENTS SHALL BE SEPARATED FROM THE INTERIOR OF |
| THE BUILDING BY WALLS OR ROOFS OF NONCOMBUSTIBLE OR |
| LIMITEDCOMBUSTIBLE |
| CONSTRUCTION. |
| 8.15.1.2.18.4 COMBUSTIBLE SOFFITS, EAVES, OVERHANGS, |
| AND DECORATIVE |
| FRAME ELEMENTS SHALL HAVE NO OPENINGS OR UNPROTECTED |
| PENETRATIONS DIRECTLY INTO THE BUILDING. |
| |
| PLEASE REVIEW AND PROVIDE HEAD COVERAGE OR JUSTIFY WITH |
| SPECIFIC FIRE CODE DETAILS. |
| |
| |
| |
| 6) THERE ARE NO INDICATIONS OF HOW THIS FIRE SPRINKLER |
| SYSTEM WILL BE MONITORED AND WHERE THE FACP WILL BE |
| LOCATED. |
| |
| PLEASE REVIEW AND PROVIDE DETAILS. |
| |
| |
| |
| 7) THERE ARE NO INDICATIONS OF THE INSTALL OF THE |
| KITCHEN HOOD AND/OR FIRE SUPPRESSION SYSTEM. |
| |
| THE KITCHEN HOOD AND FIRE SUPPRESSION SHALL BE |
| SUBMITTED UNDER SEPARATE SHOP DRAWINGS EACH IN |
| COMPLIANCE WITH NFPA 96 & 2001. |
| |
| PLEASE PROVIDE AND APPLICABLE NOTE OF ACKNOWLEDGMENT |
| AND COMPLIANCE. |
| |
| |
| |
| 8) THERE IS A CHLORINE STORAGE ROOM THAT DOES APPEAR TO |
| BE PROTECTED PER THE REQUIREMENT. |
| |
| PER NFPA 101, CHAPTER 12 NEW ASSEMBLY OCCUPANCIES |
| |
| 12.3.2 PROTECTION FROM HAZARDS. |
| 12.3.2.1 SERVICE EQUIPMENT, HAZARDOUS OPERATIONS OR |
| PROCESSES, AND STORAGE FACILITIES. |
| 12.3.2.1.2 ROOMS OR SPACES FOR THE STORAGE, PROCESSING, |
| OR USE OF |
| MATERIALS SPECIFIED IN 12.3.2.1.2(1) THROUGH (3) SHALL |
| BE PROTECTED |
| IN ACCORDANCE WITH ONE OF THE FOLLOWING: |
| (1) SEPARATION FROM THE REMAINDER OF THE BUILDING BY |
| FIRE BARRIERS |
| HAVING A MINIMUM 1-HOUR FIRE RESISTANCE RATING OR |
| PROTECTION |
| OF SUCH ROOMS BY AUTOMATIC EXTINGUISHING SYSTEMS AS |
| SPECIFIED IN SECTION 8.7 IN THE FOLLOWING AREAS: |
| (C) ROOMS OR SPACES USED FOR THE STORAGE OF HAZARDOUS |
| MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS IN |
| QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS |
| |
| PLEASE REVIEW AND CORRECT WITH SPECIFIC DETAILS. |
| |
| |
| 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |