2018-05-22 13:23:51THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A 0.0.02 - THERE IS A NOTE, UNDER BUIOLDING
 CODE DATA, INDICATING "TYPE VB NONSPRINKLERED" YET
 THERE A FIRE PROTECTION DOCUMENTS SHOWING FIRE
 SPRINKLERS.
  
 PLEASE CORRECT OR JUSTIFY.
  
  
  
 2) SHEET A 0.0.02 - UNDER "PROJECTS COMPONENTS,
 BUILDING OCCUPANCY" TABLE THERE ARE NO FIGURES ENTERED
 INTO THE COLUMNS LABLED "FACTOR OR PERSONS".
  
  
 PLEASE CORRECT
  
  
  
 3) SHEET FP 0.0.00 - UNDER THE SECTION "FIRE PROTECTION
 FLOW TEST DATA" THERE ARE NO FIGURES ENTERED INTO AREAS
 INDICATED. THESE FIGURES ARE REQUIRED TO PROVIDE
 ADAQUATE WATER SUPPLY AND SYSTEM DEMANDS.
  
 PLEASE CORRECT.
  
  
  
 4) SHEET FP 0.0.00 - UNDER THE SECTION " DESIGN
 CRITERIA" STORAGE, MECH/ELECT. ROOMS, ORDINARY HAZARD
 GRUOP 1 IS INDICATED. HOWEVER, ON SHEET FP 1.3.01 THERE
 ARE NO HEASD INDICATED IN THE ELECTRICAL ROOM.
  
 PER NFPA 13
  
 8.15.11 ELECTRICAL EQUIPMENT.
 8.15.11.1 UNLESS THE REQUIREMENTS OF 8.15.11.3 ARE MET,
 SPRINKLER
 PROTECTION SHALL BE REQUIRED IN ELECTRICAL EQUIPMENT
 ROOMS.
 8.15.11.2 HOODS OR SHIELDS INSTALLED TO PROTECT
 IMPORTANT
 ELECTRICAL EQUIPMENT FROM SPRINKLER DISCHARGE SHALL BE
 NONCOMBUSTIBLE.
 8.15.11.3 SPRINKLERS SHALL NOT BE REQUIRED IN
 ELECTRICAL EQUIPMENT
 ROOMS WHERE ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE ROOM IS DEDICATED TO ELECTRICAL EQUIPMENT ONLY.
 (2) ONLY DRY-TYPE ELECTRICAL EQUIPMENT IS USED.
 (3) EQUIPMENT IS INSTALLED IN A 2-HOUR FIRE-RATED
 ENCLOSURE
 INCLUDING PROTECTION FOR PENETRATIONS.
 (4) NO COMBUSTIBLE STORAGE IS PERMITTED TO BE STORED IN
 THE
 ROOM.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY.
  
  
  
 5) SHEET 1.3.01 - THERE APPEARS TO BE NO SPRINKLER HEAD
 COVERAGE IN THE FRONT PORCH BAR AREA.
  
 PER NFPA 13
  
 8.15.1.2.18 SOFFITS, EAVES, OVERHANGS, AND DECORATIVE
 FRAME
 ELEMENTS. SPRINKLERS SHALL BE PERMITTED TO BE OMITTED
 FROM
 WITHIN COMBUSTIBLE SOFFITS, EAVES, OVERHANGS, AND
 DECORATIVE
 FRAME ELEMENTS THAT ARE CONSTRUCTED IN ACCORDANCE WITH
 8.15.1.2.18.1 THROUGH 8.15.1.2.18.4.
 8.15.1.2.18.1 COMBUSTIBLE SOFFITS, EAVES, OVERHANGS,
 AND DECORATIVE
 FRAME ELEMENTS SHALL NOT EXCEED 4 FT 0 IN. (1.2 M) IN
 WIDTH.
 8.15.1.2.18.2 COMBUSTIBLE SOFFITS, EAVES, OVERHANGS,
 AND DECORATIVE
 FRAME ELEMENTS SHALL BE DRAFTSTOPPED, WITH A MATERIAL
 EQUIVALENT TO THAT OF THE SOFFIT, INTO VOLUMES NOT
 EXCEEDING 160 FT3
 (4.5 M3).
 8.15.1.2.18.3 COMBUSTIBLE SOFFITS, EAVES, OVERHANGS,
 AND DECORATIVE
 FRAME ELEMENTS SHALL BE SEPARATED FROM THE INTERIOR OF
 THE BUILDING BY WALLS OR ROOFS OF NONCOMBUSTIBLE OR
 LIMITEDCOMBUSTIBLE
 CONSTRUCTION.
 8.15.1.2.18.4 COMBUSTIBLE SOFFITS, EAVES, OVERHANGS,
 AND DECORATIVE
 FRAME ELEMENTS SHALL HAVE NO OPENINGS OR UNPROTECTED
 PENETRATIONS DIRECTLY INTO THE BUILDING.
  
 PLEASE REVIEW AND PROVIDE HEAD COVERAGE OR JUSTIFY WITH
 SPECIFIC FIRE CODE DETAILS.
  
  
  
 6) THERE ARE NO INDICATIONS OF HOW THIS FIRE SPRINKLER
 SYSTEM WILL BE MONITORED AND WHERE THE FACP WILL BE
 LOCATED.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 7) THERE ARE NO INDICATIONS OF THE INSTALL OF THE
 KITCHEN HOOD AND/OR FIRE SUPPRESSION SYSTEM.
  
 THE KITCHEN HOOD AND FIRE SUPPRESSION SHALL BE
 SUBMITTED UNDER SEPARATE SHOP DRAWINGS EACH IN
 COMPLIANCE WITH NFPA 96 & 2001.
  
 PLEASE PROVIDE AND APPLICABLE NOTE OF ACKNOWLEDGMENT
 AND COMPLIANCE.
  
  
  
 8) THERE IS A CHLORINE STORAGE ROOM THAT DOES APPEAR TO
 BE PROTECTED PER THE REQUIREMENT.
  
 PER NFPA 101, CHAPTER 12 NEW ASSEMBLY OCCUPANCIES
  
 12.3.2 PROTECTION FROM HAZARDS.
 12.3.2.1 SERVICE EQUIPMENT, HAZARDOUS OPERATIONS OR
 PROCESSES, AND STORAGE FACILITIES.
 12.3.2.1.2 ROOMS OR SPACES FOR THE STORAGE, PROCESSING,
 OR USE OF
 MATERIALS SPECIFIED IN 12.3.2.1.2(1) THROUGH (3) SHALL
 BE PROTECTED
 IN ACCORDANCE WITH ONE OF THE FOLLOWING:
 (1) SEPARATION FROM THE REMAINDER OF THE BUILDING BY
 FIRE BARRIERS
 HAVING A MINIMUM 1-HOUR FIRE RESISTANCE RATING OR
 PROTECTION
 OF SUCH ROOMS BY AUTOMATIC EXTINGUISHING SYSTEMS AS
 SPECIFIED IN SECTION 8.7 IN THE FOLLOWING AREAS:
 (C) ROOMS OR SPACES USED FOR THE STORAGE OF HAZARDOUS
 MATERIALS OR FLAMMABLE OR COMBUSTIBLE LIQUIDS IN
 QUANTITIES DEEMED HAZARDOUS BY RECOGNIZED STANDARDS
  
 PLEASE REVIEW AND CORRECT WITH SPECIFIC DETAILS.
  
  
 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  