Plan Review Notes
Plan Review Notes For Permit 18050277
Permit Number 18050277
Review Stop B
Sequence Number 1
Notes
Date Text
2018-06-27 06:53:20****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC B TABLES 705.2, 705.8, PROJECT DATA SHEET STATES
 THAT THE DISTANCE TO OTHER STRUCTURES IS OVER 30'.
 REVISE SITE PLAN TO SHOW DISTANCE TO ASSUMED PROPERTY
 LINE BETWEEN THE PERGOLA, GAZEBO, OR IS INTENT TO
 UTILIZE EXCEPTION (FBC B 705.2 EXCEPTION)? REVISE PLAN
 TO SHOW COMPLIANCE.
  
 2 A1.0.04, HOW OCCPUANT LOAD OF 106 WAS DETERMINED IS
 NOT CLEAR.
  
 3. FBC 109, VALUE IS TO INCLUDE ALL LABOR, MATERIALS,
 OVERHEAD, PROFIT, DESIGN FEES; EVERYTHING EXCEPT FOR
 LAND. SOME ITEMS ON THE PLAN ARE SHOWN "BY OWNER"; IF
 THESE ITEMS ARE PERMANENTLY INSTALLED, THEY ARE TO BE
 INCLUDED IN PERMIT VALUE. WHEN RESUBMITTING, PROVIDE
 THE CORRECT VALUE AND PAY PLAN REVIEW FEES ON CORRECTED
 VALUE.
  
 NOTE THAT REVIEWS BY ALL TRADES MAY NOT HAVE BEEN DONE
 AT THIS TIME PENDING PAYMENT OF PLAN REVIEW FEES.
  
 4. A5.0.00, ROOM FINISH WALLS FOR BATHROOMS ARE SHOWN
 AS GYP/PAINT; SEE FBC B 1210.2.1, 1210.2.2, REVISE PLAN
 TO SHOW COMPLIANCE.
  
 5. A7.0.01 IS TOO LIGHT TO READ; PLEASE ADJUST, FBC
 107.
  
 6. FBC 107, WILL THIS BUILDING BE SPRINKLERED?
 CONFLICTING INFORMATION ON PLANS; SEE FIRE REVIEW.
  
  
  