Date Text
2018-07-05 17:26:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC R 301
  
 1-2. OK
  
 3. PANELS: SHEET 1 SPECIFIES 12D EDGE DISTANCE OR PER
 MANUFACTURER SPEC. 3" REQUIRED FOR A 1/4" ANCHOR.
 MANUFACTURER SPEC ONLINE REQUIRES 3-3/4" WITH REDUCTION
 FACTOR FOR OTHER EDGE DISTANCES. REVISE THE
 INSTALLATION SCHEDULE TO SPEC FASTENER DIAMETER AND
 REVISE EDGE DISTANCE ACCORDINGLY. SPEC SHEET FROM
 MANUFACTURER MAY BE REQUIRED.
  
 4. WINDOWS AND SHUTTERS SPANS ARE SPECIFIED AS WIDTH X
 HEIGHT. THE SHUTTER ORIENTATION (HORIZ/VERT) FOR THE
 PANELS IS NOT CONSISTENT WITH THE SPANS AND OPENING
 SIZE. FOR INSTANCE: OPENING 1, 86.25 X 54, HORIZONTAL,
 54" SPAN. THE 54" DIMENSION IS THE WINDOW HEIGHT.
  
 COMPLIANCE NOT CLEAR. FOR INSTANCE: OPENING 7, 116.25
 WIDTH. SPAN IS 49", BUT THAT IS THE HEIGHT. IF SPAN IS
 ACTUALLY 116.25, PER SHEET2 THIS SPAN IS LIMITED TO
 -30PSF.
  
 5. IT IS NOT CLEAR WHICH INSTALLATION METHOD IS
 PROPOSED; DIRECT MOUNT AT BOTH ENDS, OR DIRECT MOUNT AT
 ONE END ONLY.
  
  
  