Plan Review Notes For Permit 18050186 |
Permit Number |
18050186 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-05-26 11:06:32 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. FROM PREVIOUS LIST: PROVIDE A PLAN TO SHOW MEANS OF | | ESCAPE REQUIRED BY FBC R 310.4; INCLUDE ROOM | | DESIGNATION. | | | | IT IS NOT CLEAR HOW THIS WAS ADDRESSED AS NONE OF THE | | OPENINGS ARE NOTED AS "EGRESS"; PLEASE REVISE. | | | | 2. FL17733 IS VERY DIFFICULT TO READ; IS IT POSSIBLE TO | | OBTAIN A LEGIBLE DOCUMENT FROM THE INTERNET? FBC 107. | | | | 3. THE PANELS ARE NOTED AS HORIZONTAL INSTALLATION, | | CONCRETE. UNLESS THIS HOUSE IS FORMED AND POURED | | CONCRETE, THE WINDOW OPENINGS HAVE FILLED CELLS | | (CONCRETE BLOCK SUBSTRATE). PLEASE VERIFY AND REVISE IF | | NECESSARY. | | | | IT IS POSSIBLE THAT THE RESUBMITTAL WILL BE ACCEPTED | | VIA EMAIL; PLEASE EMAIL CORRECTED DOCUMENTS DIRECTLY TO | | ME IN THE NEXT WEEK WITH THE PERMIT NUMBER IN THE | | SUBJECT LINE AND "RESUBMITTAL". IF RESUBMITTED AFTER | | THE NEXT WEEK, PLEASE SUBMIT AT THE COUNTER. | | | | IF APPLICANT PREFERS PAPER RESUBMITTAL, THAT IS | | ACCEPTABLE. | | | | 4. NOTICE - AFTER REVIEW HAS PASSED, THIS PERMIT WILL | | BE ISSUED VIA EMAIL. PLEASE NOTIFY IF CONTRACTOR | | OBJECTS. | | | | | | |
|