Plan Review Notes For Permit 18050114 |
Permit Number |
18050114 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-05-03 17:40:52 | 05/03/2016 1ST PLUMBING REVIEW**DENIED** | | | | 1) CLEAN OUT REQUIRED ON MAIN HOUSE. REVISE YOUR | | ISOMETRIC TO COMPLY WITH FBC-R P3005.2.3 | | | | 2) A STUDOR VENT ON THE GUEST HOUSE IS NOT PERMITTED. | | THE VENT SYSTEM SERVICING EACH BUILDING DRAIN SHALL NOT | | HAVE LESS THEN 1 VENT THAT EXTENDS TO THE OUTDOORS. | | FBC-R P 3102.1 | | | | 3) SHOW FIXTURE LOAD (DFU'S)ON EACH BRANCH LINE SIZING | | WITH TABLE FBC-R P3004.1 | | | | 4) SHOW FIXTURE LOAD (DFU'S) ON SEWER LINE SIZING USING | | TABLE FBC-R P 3005.4.2 | | | | 5) TESTING OF ALL NEW WORK WILL COMPLY FULLY WITH FBC-R | | P SECTION 2503 REQUIRING A HEAD TEST ALEAST UP TO THE | | POINT OF EXISTING FITTING'S. THIS IS NOT A MUILT | | DWELLING APARTMENT BUILDING BUT A SINGLE FAMILY HOME | | PERMITTED UNDER #15081144 C.O WAS GIVEN ON 04/20/2017 | | AS A SINGLE FAMILY OCCUPANCY. THE INSPECTOR WILL WORK | | AROUND THE FAMILY'S SCHEDULE TO ACCOMMODATETHE TIME YOU | | WILL NEED TO TEST. | | | | 6) PLANS DRAWN IN PENCIL ARE NOT PERMITTED AND DO NOT | | MEET MIN PLAN REVIEW CRITERIA. FBC 107.3.5 | | | | | | TIM HUNT | | PLUMBING INSPECTOR / PLUMBING PLAN REVIEWER | | CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | 561-805-6695 | | [email protected] | | |
|