2018-05-03 19:16:33 | 05/03/18 DENIED BY PLUMBING | | | | 1. THIS DEVICE IS NOT LEAD FREE THE XL2 IS SO PLEASE | | PROVIDE DOCUMENTATION THAT THE PROPOSED BACKFLOW DEVICE | | IS ON THE APPROVED DEVICE LIST PUBLISHED BY THE | | UNIVERSITY OF SOUTHERN CALIFORNIA (USC). PLEASE CONTACT | | DEPARTMENT OF PUBLIC UTILITY FIELD CUSTOMER SERVICE AT | | 561-822-2240 FOR DOCUMENTED CONFIRMATION THAT THE | | PROPOSED BACKFLOW PREVENTION DEVICE COMPLIES WITH CITY | | REQUIREMENTS | | | | 2. A SITE PLAN DEPICTING THE GENERAL LOCATION OF THE | | PROPOSED BACKFLOW PREVENTION DEVICE. | | | | 3. TWO COPIES OF THE MANUFACTURER?S SPECIFICATIONS FOR | | THE BACKFLOW PREVENTER. THE MAKE, MODEL, AND SIZE OF | | THE DEVICE SHALL BE LISTED IN THE DESCRIPTION OF WORK | | SECTION ON THE PERMIT APPLICATION. | | | | 4. DOCUMENTATION THAT THE PROPOSED DEVICE IS LEAD-FREE. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | [email protected] | | 561-805-6720 | | |
|