Plan Review Notes
Plan Review Notes For Permit 18050054
Permit Number 18050054
Review Stop E
Sequence Number 1
Notes
Date Text
2018-05-03 13:04:22FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 AIC RATING FOR THE SERVICE.
 PROVIDE CALCULATION FOR AVAILABLE SHORT CIRCUIT CURRENT
 AT NEW PANEL TO CONFIRM AIC RATING IS ADEQUATE. NEC
 110.10
  
 PLEASE SHOW LOCATION OF ANY OTHER SERVICES ON THE
 BUILDING. 230.72 FOR GROUPING OF MAINS.
  
 PLEASE SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF THE
 PANEL IN THE BUILDING.
  
  
  