2018-07-25 06:24:37ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. 5TH PLAN REVIEW WITH SAME DEFICIENCIES. THERE WILL
 BE NO FURTHER PLAN REVIEWS OF THIS PERMIT (FOR
 ELECTRICAL) UNTIL I HAVE SPOKEN TO EITHER THE QUALIFIER
 FOR FERRIGN SIGNS OR THE ENGINEER OF RECORD FOR THIS
 PROJECT. PLEASE CONTACT ME DIRECTLY ON MY CELL PHONE
 561-657-1653
  
 2. HIGH VOLTAGE AND LOW VOLTAGE TOGETHER IN J-BOX.
 725.136B NEC
  
 3. DISCONNECT REQUIRED AS PER NEC 600.6A1
  
 4. DUE TO THE DISCONNECT REQUIREMENTS OF 600.6A(1) NEC
 AN ELEC SUB-PERMIT CAN'T BE ISSUED TO AN ES LICENSE
 HOLDER BECAUSE IT IS OUT OF THE SCOPE OF WORK FOR THEIR
 LICENSE.
  
 SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C.
 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN
 SPECIALTY CONTRACTOR)
  
 THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL
 FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION,
 INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF
 ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF
 CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR
 ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR
 TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER
 THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE
 REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE
 BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY
 STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN
 TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250)
 VOLTS MAXIMUM.
  
 5. THERE IS A NOTE ON THE PLAN THAT STATES "TIME CLOCK
 IS EXISTING" TIME CLOCK MUST STILL CONFORM TO FBC CE
 405.2.4 (ASTRONOMICAL TIME CLOCK NEEDED)
  
 6. SIGNATURE AND SEAL ON PLAN IS PHOTO COPIED. NOT
 CONSIDERED TO BE SIGNED AND SEALED.
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  