2018-07-25 06:24:37 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. 5TH PLAN REVIEW WITH SAME DEFICIENCIES. THERE WILL |
| BE NO FURTHER PLAN REVIEWS OF THIS PERMIT (FOR |
| ELECTRICAL) UNTIL I HAVE SPOKEN TO EITHER THE QUALIFIER |
| FOR FERRIGN SIGNS OR THE ENGINEER OF RECORD FOR THIS |
| PROJECT. PLEASE CONTACT ME DIRECTLY ON MY CELL PHONE |
| 561-657-1653 |
| |
| 2. HIGH VOLTAGE AND LOW VOLTAGE TOGETHER IN J-BOX. |
| 725.136B NEC |
| |
| 3. DISCONNECT REQUIRED AS PER NEC 600.6A1 |
| |
| 4. DUE TO THE DISCONNECT REQUIREMENTS OF 600.6A(1) NEC |
| AN ELEC SUB-PERMIT CAN'T BE ISSUED TO AN ES LICENSE |
| HOLDER BECAUSE IT IS OUT OF THE SCOPE OF WORK FOR THEIR |
| LICENSE. |
| |
| SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C. |
| 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN |
| SPECIALTY CONTRACTOR) |
| |
| THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL |
| FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION, |
| INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF |
| ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF |
| CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR |
| ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR |
| TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER |
| THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE |
| REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE |
| BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY |
| STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN |
| TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250) |
| VOLTS MAXIMUM. |
| |
| 5. THERE IS A NOTE ON THE PLAN THAT STATES "TIME CLOCK |
| IS EXISTING" TIME CLOCK MUST STILL CONFORM TO FBC CE |
| 405.2.4 (ASTRONOMICAL TIME CLOCK NEEDED) |
| |
| 6. SIGNATURE AND SEAL ON PLAN IS PHOTO COPIED. NOT |
| CONSIDERED TO BE SIGNED AND SEALED. |
| |
| PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE |
| LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE?S |
| SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR |
| COPIED IMAGE OF THE LICENSEE?S SIGNATURE IS NOT ALLOWED |
| ON PHYSICALLY TRANSMITTED DOCUMENTS. |
| CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL |
| SIGN BY HAND AN ORIGINAL OF THE LICENSEE?S SIGNATURE ON |
| EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE, |
| DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE?S |
| SIGNATURE SHALL NOT BE USED. |
| |
| AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED |
| DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A |
| WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART |
| OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO |
| PARTIALLY OVERLAP THE LICENSEE?S SIGNATURE SUCH THAT |
| THE SIGNATURE IS NOT MADE ILLEGIBLE. |
| CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN |
| USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN |
| EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE |
| LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE |
| SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE |
| SIGNATURE ILLEGIBLE. |
| |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WPB |
| [email protected] |
| CELL: 561-657-1653 |
| |