Date |
Text |
2018-07-13 06:25:55 | SAME VIOLATIONS AS PREVIOUS PLAN REVIEW. PLEASE SEE |
| COMMENTS BELOW. |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PLAN STILL DOES NOT MEET DISCONNECT REQUIRMENTS OF |
| 600.6A(1) NEC. |
| |
| 2. DUE TO THE DISCONNECT REQUIREMENTS OF 600.6A(1) NEC |
| AN ELEC SUB-PERMIT CAN'T BE ISSUED TO AN ES LICENSE |
| HOLDER BECAUSE IT IS OUT OF THE SCOPE OF WORK FOR THEIR |
| LICENSE. |
| |
| SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C. |
| 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN |
| SPECIALTY CONTRACTOR) |
| THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL |
| FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION, |
| INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF |
| ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF |
| CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR |
| ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR |
| TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER |
| THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE |
| REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE |
| BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY |
| STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN |
| TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250) |
| VOLTS MAXIMUM. |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WPB |