2018-06-04 07:22:29ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. INITIAL PLAN FAILED DUE TO THE NEED FOR A DISCONNECT
 AND VALUE BEING TOO LOW. NOW A NEW PLAN HAS BEEN
 SUBMITTED SEPARATELY WITH A DIFFERENT SIGN CONTRACTOR
 NAME (RAMSAY) INSTEAD OF FERRIN SIGNS AS IS ON PERMIT
 APPLICATION. CORRECT CONFLICTING ERRORS ON PLANS.
 CANNOT HAVE 2 DIFFERENT PLANS, ZONING AND BUILDING MUST
 REVIEW NEW PLAN SUBMITTED.
  
 2. NEW PLAN SUBMITTED IS NOT SIGNED. ELECTRICAL PLAN IS
 REQUIRED TO BE DESIGNED AND SIGNED/SEALED BY A DESIGN
 PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER.
 PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC
 107.1
  
 3. VALUE TOO LOW, PROVIDE COPY OF SIGNED CONTRACT WITH
 SCOPE AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND
 LABOR. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  