2018-06-04 07:22:29 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. INITIAL PLAN FAILED DUE TO THE NEED FOR A DISCONNECT |
| AND VALUE BEING TOO LOW. NOW A NEW PLAN HAS BEEN |
| SUBMITTED SEPARATELY WITH A DIFFERENT SIGN CONTRACTOR |
| NAME (RAMSAY) INSTEAD OF FERRIN SIGNS AS IS ON PERMIT |
| APPLICATION. CORRECT CONFLICTING ERRORS ON PLANS. |
| CANNOT HAVE 2 DIFFERENT PLANS, ZONING AND BUILDING MUST |
| REVIEW NEW PLAN SUBMITTED. |
| |
| 2. NEW PLAN SUBMITTED IS NOT SIGNED. ELECTRICAL PLAN IS |
| REQUIRED TO BE DESIGNED AND SIGNED/SEALED BY A DESIGN |
| PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. |
| PROVIDE CORRECTION. FS 471.003(2)(H); 471.025; WPB FBC |
| 107.1 |
| |
| 3. VALUE TOO LOW, PROVIDE COPY OF SIGNED CONTRACT WITH |
| SCOPE AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND |
| LABOR. FBC 109.3 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |