Notes |
Date |
Text |
2018-05-14 03:27:58 | 1) SHT.1 OF 3 - GENERAL NOTE #6 - STATES "DISPOSAL OF | | WATER WILL CONFORM TO FBC 2017 E4204." THIS CODE | | SECTION IS FROM THE 2017 FBC-RESIDENTIAL CODE AND THIS | | SECTION IS FOR POOL BONDING. CLARIFY. | | 2) SHT. 2 OF 3 - ELECTRICAL SCHEMATIC DIAGRAM SHOWS AN | | OPTIONAL GAS HEATER BUT THE PROJECT SPECIFIC DETAILS ON | | SHT.1 OF 3 REFERS TO AN ELECTRIC HEATER. CLARIFY. | | 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | SPECIFICATIONS FOR THE MAIN DRAINS. WPB AMEND. TO FBC | | SEC. 107.2.1. | | 4) IT APPEARS THAT THE TOTAL DYNAMIC HEAD CALCULATIONS | | WERE BASED ON THE MAXIMUM FLOW RATE OF THE PUMP.SUBMIT | | TOTAL DYNAMIC HEAD CALCULATIONS FOR THE MAXIMUM SYSTEM | | FLOW. THE MAXIMUM FLOW OF THE PUMP FROM ITS PUMP CURVE | | IS NO LONGER ALLOWED TO BE USED IN DETERMINING MAXIMUM | | SYSTEM FLOW RATE PER ANSI/APSP/ICC 7 ? 2013 SECS. | | 4.4.9, 4.4.9.1. THE 2013 EDITION ADDRESSES FLOW RATE IN | | GALLONS PER MINUTE (GPM). IT REQUIRES THAT MAXIMUM | | SYSTEM FLOW RATE DOES NOT EXCEED THE LISTED MAXIMUM | | FLOW RATE OF THE SUCTION OUTLET FITTING ASSEMBLY (DRAIN | | COVER). | | 5) SHT.1 OF 3 - GENERAL NOTE #3 REFERS TO THE 2014 FBC. | | REVISE NOTE TO READ 2017 FBC. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | CITY OF WEST PALM BEACH | | 561-805-6692 | | [email protected] | | | | | | | | | | | | | | | | |
|