Plan Review Notes
Plan Review Notes For Permit 18050029
Permit Number 18050029
Review Stop P
Sequence Number 1
Notes
Date Text
2018-05-14 03:56:461) SHT.1 OF 3 - GENERAL NOTE #6 - STATES "DISPOSAL OF
 WATER WILL CONFORM TO FBC 2017 E4204." THIS CODE
 SECTION IS FROM THE 2017 FBC-RESIDENTIAL CODE AND THIS
 SECTION IS FOR POOL BONDING. CLARIFY.
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE MAIN DRAINS. WPB AMEND. TO FBC
 SEC. 107.2.1.
 3) IT APPEARS THAT THE TOTAL DYNAMIC HEAD CALCULATIONS
 WERE BASED ON THE MAXIMUM FLOW RATE OF THE PUMP.SUBMIT
 TOTAL DYNAMIC HEAD CALCULATIONS FOR THE MAXIMUM SYSTEM
 FLOW. THE MAXIMUM FLOW OF THE PUMP FROM ITS PUMP CURVE
 IS NO LONGER ALLOWED TO BE USED IN DETERMINING MAXIMUM
 SYSTEM FLOW RATE PER ANSI/APSP/ICC 7 ? 2013 SECS.
 4.4.9, 4.4.9.1. THE 2013 EDITION ADDRESSES FLOW RATE IN
 GALLONS PER MINUTE (GPM). IT REQUIRES THAT MAXIMUM
 SYSTEM FLOW RATE DOES NOT EXCEED THE LISTED MAXIMUM
 FLOW RATE OF THE SUCTION OUTLET FITTING ASSEMBLY (DRAIN
 COVER).
 4) SHT.1 OF 3 - GENERAL NOTE #3 REFERS TO THE 2014 FBC.
 REVISE NOTE TO READ 2017 FBC.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-805-6692
 [email protected]
  
  
  
  
  
  
  
  