2018-06-04 03:05:591) SHOW THE DISTANCE FROM THE OUTLET OF THE GAS METER
 TO THE MP REGULATOR FOR THE EXISTING INTERIOR LOAD.
 2017 FBC- FUEL GAS SEC.402.4.1.
 2) SHOW THE DISTANCE FROM THE OUTLET OF THE MP
 REGULATOR TO THE MOST REMOTE GAS OUTLET ON THE INTERIOR
 SECTION OF THE SYSTEM. 2017 FBC- FUEL GAS SEC.402.4.1.
 3) THE SHUTOFF VALVE ON THE LINE INTO THE STRUCTURE
 SHALL BE LOCATED IMMEDIATELY AHEAD OF THE REGULATOR.
 2017 FBC-FUEL GAS SEC. 409.4.
 4) THERE IS A GAS GRILL SHOWN ON THE ORIGINAL SET OF
 GAS PLANS ( PERMIT #99060584) ON FILE WITH THE CITY.
 THIS GRILL IS NOT SHOWN ON THE NEWLY SUBMITTED GAS
 PLAN. CLARIFY.
 5) THE EXISTING PLANS ON FILE WITH THE CITY FOR THIS
 ADDRESS SHOW THE LONGEST RUN AS 110 FEET. CLARIFY.
  