Plan Review Notes For Permit 18050026 |
Permit Number |
18050026 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-06-04 03:05:59 | 1) SHOW THE DISTANCE FROM THE OUTLET OF THE GAS METER | | TO THE MP REGULATOR FOR THE EXISTING INTERIOR LOAD. | | 2017 FBC- FUEL GAS SEC.402.4.1. | | 2) SHOW THE DISTANCE FROM THE OUTLET OF THE MP | | REGULATOR TO THE MOST REMOTE GAS OUTLET ON THE INTERIOR | | SECTION OF THE SYSTEM. 2017 FBC- FUEL GAS SEC.402.4.1. | | 3) THE SHUTOFF VALVE ON THE LINE INTO THE STRUCTURE | | SHALL BE LOCATED IMMEDIATELY AHEAD OF THE REGULATOR. | | 2017 FBC-FUEL GAS SEC. 409.4. | | 4) THERE IS A GAS GRILL SHOWN ON THE ORIGINAL SET OF | | GAS PLANS ( PERMIT #99060584) ON FILE WITH THE CITY. | | THIS GRILL IS NOT SHOWN ON THE NEWLY SUBMITTED GAS | | PLAN. CLARIFY. | | 5) THE EXISTING PLANS ON FILE WITH THE CITY FOR THIS | | ADDRESS SHOW THE LONGEST RUN AS 110 FEET. CLARIFY. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | | | |
|