2018-05-14 05:16:57 | |
| 1) SHOW THE TYPE OF PIPE AND PIPE SIZE AT THE OUTLET OF |
| THE 2 PSI METER . WPB AMEND. TO FBC SEC. 107.2.1. |
| 2) SHOW THE PIPE SIZE OF THE SECTION OF PIPE TO THE |
| REGULATOR SERVING THE EXISTING GAS LOAD.WPB AMEND. TO |
| FBC SEC. 107.2.1. |
| 3) SHOW THE TYPE OF PIPE AND PIPE SIZE DOWNSTREAM OF |
| THE REGULATOR FOR THE EXISTING GAS LOADS AND NOTE THE |
| DISTANCE FROM THIS REGULATOR TO THE FURTHEST OUTLET ON |
| THAT SYSTEM.WPB AMEND. TO FBC SEC. 107.2.1. |
| 4) A LISTED SHUTOFF VALVE IS REQUIRED IMMEDIATELY AHEAD |
| OF THE MP REGULATOR FFOR THE EXISTING LOADS.. 2017 FBCR |
| SEC. G2420.4. |
| 5) SPECIFY ON THE GAS DRAWING HOW THE 3/4 INCH |
| GALVANIZED PIPE IS GOING TO BE INSTALLED. ABOVE-GROUND |
| PIPING OUTDOORS SHALL COMPLY WITH 2017 FBCR |
| SEC.G2415.9, G2415.11. |
| 6) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE FLEX |
| CONNECTOR FOR THE GENERATOR. THE FLEX CONNECTOR SHALL |
| BE APPROVED TO FLOW THE MAXIMUM BTU LOAD FOR THE |
| GENERATOR. 2017 FBCR SEC. G2422.1 (8). |
| 7) THE SEDIMENT TRAP AS DRAWN DOES NOT COMPLY WITH 2017 |
| FBCR SEC.G2419.4. |
| 8) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| INSTALLATION SHEETS FOR THE REGULATORS. REGULATORS |
| INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| APPROVED FOR OUTDOOR INSTALLATION. 2017 FBCR |
| SEC.G2421.1, FBC-FUEL GAS SEC. 410.1. |
| 9) LIST THE EXISTING GAS FIXTURES ON THE PLAN AND THE |
| CORRESPONDING BTU LOAD FOR EACH APPLIANCE. WPB AMEND. |
| TO FBC SEC .107.2.1, 2017 FBC-FUEL GAS SEC.402.1. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |